
PT610, PT620, PT630
Instruction Manual
66
6.2.4.6 [139 ADDRESS] – Port address
00 to 99 (01 default, 00 = transmission without address)
6.2.5 [15_] – Ethernet TCP/IP
This sub-block includes the parameters related to the built in Ethernet interface of the PT630.
Note:
Not present on PT610, PT620. Can be installed as an option card for PT610 under
[19-]
.
6.2.5.1 [151 FORMAT] – Data Format
+
NO = Port is disabled
CONT = Continuous data output
FAST = High speed continuous data output PRNT = Printout
BSI = BSI format for PC, PLC interface
BARC = Bar code reader, ID device
MBHL = Modbus RTU High-Low format
MBLH = Modbus RTU Low-High format
6.2.5.2 [152 IP] – IP Address
Enter the IP address with the keypad. The default is “192.168.16.250”.
6.2.5.3 [153 ADDRESS] – Device Address
Enter a value between 000 and 255, 000 = transmission without an address for the device.
6.2.5.4 [154 SUB MASK] – Subnet Mask
Enter the subnet mask. The default is “255.255.255.0”.
6.2.5.5 [155 GATEWAY] – Gateway Address
Enter the IP address of the gatewaywith the keypad. The default is “192.168.16.253”.
6.2.5.6 [156 LOCAL P1] – Local Port 1
Enter a value between 00001 and 65535 for the device. The default is “00502”. This is a protected port
on some systems and you may need to change to a value above “01024”
6.2.5.7 [157 LOCAL P2] – Local Port 2
Enter a value between 00001 and 65535 for the device. The default is “00503”. This is a protected port
on some systems and you may need to change to a value above “01024”
6.2.5.8 [158 LOCAL P3] – Local Port 3
Enter a value between 00001 and 65535 for the device. The default is “00504”. This is a protected port
on some systems and you may need to change to a value above “01024”
6.2.5.9 [159 DNS] – DNS address
Enter the address of the Domain Name Server. The default is “208.067.222.222”.
6.2.5.10 [15A MAC ADR] – MAC Address
Enter a MAC address for the port. The format is “AA=BB=CC=DD=EE=FF”
6.2.5.11 [15B TIMEOUT] – Idle timeout
Enter a value between 01 and 60 for the device. The default is “5”. “00” will disable idle timeout.
6.2.5.12 [15C CR-LF] – CR+LF
NO = no CR
+
YES = CR enabled
Enable or disable sending of the ASCII 13 folowed by ASCII 10 characters for continuous data format.
6.2.5.13 [15D Delay] – Response speed
000 to 999 miliseconds (50 default)
Data output delay for Modbus and BSI formats; delay between continuous format data packets.
Note: This property is very helpful for slow PLC systems.
6.2.5.14 [15E REMOTE IP] – Remote IP Addr.
Enter the IP address with the keypad. The default is “0.0.0.0”.
6.2.5.15 [15F REMOTE PO] – Remote Port
Enter a value between 00001 and 65535 for the device. The default is “00000”. This is a protected port
on some systems and you may need to change to a value above “01024”