PT610, PT620, PT630
Instruction Manual
63
Exiting Setup
To exit back to normal operation note the following;
•
If you press the
<ESC>
key while in a parameter, you will get out of the active sub-block and
reach the next sub-block.
•
If you press
<ESC>
key again, you will get out of the active block and reach the next main
block.
•
If you press
<ESC>
key once again, the
[SAVE : YES ]
message appears on the display.
◦
Here you can press the
<ENTER
key to save the changes into memory,
◦
or you can press the
<CHANGE>
key to show
[SAVE : NO ]
, press the
<ENTER>
key to
exit without saving,
◦
or you can press the
<CHANGE>
key to show
[SAVE : BACK ]
, press the
<ENTER>
key
to return to the main menu,
◦
or you can press the
<CHANGE>
key to show
[SAVE : TEMP ]
, press the
<ENTER>
key
to store the changes temporarily until the power goes off,
◦
or you can press the
<ESC>
key to abort changes.
•
[Waıt]
will be seen on the display for a little while, and then weighing mode is resumed.
•
Turn the power off and set the calibration DIP switch to “OFF” (the up position) before normal
operation. This is specially important for legal metrological use.
6.2 [1__] – INTERFACE PARAMETERS
Parameters relating to the communications interfaces are set in this block after entering setup (6.1).
Only the parameters for the RS-232C and RS-485 ports are shown here. Refer to the section on each
protocol (Ethernet, PROFIBUS, PROFINET, CANopen) for further information.
Note:
Default parameters are marked with a +
6.2.1 [11_] – RS-232C.1
This sub-block includes the parameters for the 1st (RS-232C) serial interface
6.2.1.1 [111 FORMAT] – Data Format
NO = Port is disabled
*CONT = Continuous data output
FAST = High speed continuous data output
+
PRNT = Printout
BSI = BSI format for PC, PLC interface
BARC = Bar code reader, ID device
MBHL = Modbus RTU High-Low format
MBLH = Modbus RTU Low-High format
Note:
BARC is not available on the PT610.
*Note:
For the RD4, RD5 and RD6 remote display interfacing, CR and LF should be enabled.
6.2.1.2 [112 BAUD] – Baud Rate
1200 = 1200
2400 = 2400
4800 = 4800
+
9600 = 9600
19K2 = 19200
38K4 = 38400
57K6 = 57600
6.2.1.3 [113 LENGTH] – Data Length
7 = 7 bits
8 = 8 bits
6.2.1.4 [114 PARITY] – Parity
+
NO = No parity
ODD = Odd parity
EVEN = Even parity
6.2.1.5 [115 CSUM] – Checksum
+
NO = no checksum
YES = checksum enabled
Enable or disable for continuous data format and BSI command mode.
6.2.1.6 [116 CR] – Carriage Return
NO = no CR
+
YES = CR enabled
Enable or disable sending of the ASCII 13 character for continuous data format.
6.2.1.7 [117 LFEED] – Line Feed
NO = no Line Feed
+
YES = Line Feed enabled
Enable or disable sending of the ASCII 10 character for continuous data format.
6.2.1.8 [118 DELAY] – Response Speed
000 to 999 miliseconds (50 default)