PT113
Instruction Manual
12
Off
Not online /No power
Check power and cable
Green
On-line, data exchange
-
Flashing Green
On-line, clear
-
Flashing Red
(2 flash)
PROFIBUS configuration error
Check GSD file configuration.
.
5.1.2.4 PT113PN
The PT113PN has 3 additional LEDs, MS, Link and NS. Their meaning is described below.
MS Module Status LED
LED State
Description
Comment
Off
No power or not initialised
No power to the device or Profinet
module is not in an initialised state
Green
Initialised
Green, 1 flash
Initialised, diagnostic event(s) are present
Diagnostic is active
Red
Exception error
There is an exception error
Red, 1 flash
Configuration Error
Check GSDML configuration
Red, 2 flashes
IP Address Error
IP address not set
Red, 3 flashes
Station Name Error
Station name not set
Red, 4 flashes
Internal Module Error
Re-energize the instrument.
If seen again, change the PT113PN.
LINK/Activity LED
LED State
Description
Comment
Off
No Link
No link, no communication present
Green
Link
Ethernet link established, no
communication present
Green,
flickering
Activity
Ethernet link established,
communication present
NS Network Status LED
LED State
Description
Comment
Off
Not online /No power
Check power and cable
Green
On-line (RUN)
-
Green, flashing
On-line (STOP)
-
5.1.2.5 PT113EI
The PT113EI has 3 additional LEDs, MS, Link and NS. Their meaning is described below.
MS Module Status LED
LED State
Description
Comment
Off
No power or not initialised
No power to the device or
EtherNet/IP module is not in an
initialised state
Green
Controlled by a scanner in run state
Green, flashing
Not configured, or scanner in idle state
Red
Major fault
EXCEPTION state, FATAL error etc.
Red, flashing
Recoverable fault(s)
Check and correct faults*
*In the case of a red Status LED warning, check cabling, configuration and IP address before
reenergising the instrument after 30 seconds power off.