background image

PSP Products, Inc.  |  8618 Phoenix Drive  |  Manassas, VA 20110  |  pspproducts.com  |  1-800-648-6802  |  [email protected]

Revised: 10/1/2021

Register Online at:

https://surgewarrantyonline.com

Important: Risk of electrical shock. This device 

should only be installed by qualified personnel.

Hurricane 4000 Series

Technical Assistance Call: 800-648-6802

After Hours Tech Support 443-600-3403

Installation Instructions 

1. Preparation for Install of Surge Protection Device 

(SPD)

A. Verify the system 

voltage and wiring 

configuration is 

the same as the 

enclosed SPD by 

metering the panel 

voltage and checking 

it against the product 

label located on the 

SPD.
B. Review the 

installation area to 

ensure the proper 

space is available to 

properly mount and 

install the SPD. The enclosure should be mounted no 

more than 3 feet away from the distribution panel.
C. Check that the buildings facility grounding system 

meets all NEC & CEC requirements as well as local 

codes. A low resistance ground system is essential to 

the proper functioning of any SPD. The soil resistance 

level should be no more than 25 ohms. This can be 

verified by performing a soil resistivity test.

2. Location of Surge Protection Device (SPD)

A. For service entrance applications, install the SPD at 

the main distribution panel on the load side after the 

main disconnect.
B. For feeder/sub-panel applications, install the SPD 

directly adjacent to the panelboard.

IMPORTANT! Remember to keep conductor 

lead length to a maximum of 3ft or less.

3. Wiring of Surge Protection Device (SPD)

A. TURN OFF the power to the distribution panel where 

the SPD will be installed.

Optional: 

I

nstall a circuit breaker to feed the SPD. 

This will allow safety personnel to remove power from 

the device in order to diagnose or service the unit. In 

addition, the device incorporates internal fusing, UL & 

CSA approved, that will protect against short circuit 

fault conditions within the unit.
B. Nipple mount SPD, or install either a rigid or flexible 

metal conduit between the SPD and the distribution 

panel.
C. Run wires of SPD to distribution panelboard - See 

wiring diagrams for details. 
D. Ensure proper color codes: Table 1.
E. Tighten and recheck all connections.
F. If remote monitoring is employed, connect the 

form “C” contacts to the building monitor system or 

independent alarm, i.e. addressable relay. Contact 

relays will accept up to 1A/220 VAC. The dry contact 

terminals are N.O. (normally open), N.C. (normally 

closed) and COM (common). Diagram 1.
NOTES: Check wiring before applying power

.

Wire

Color

Ground

Green or Green/Yellow

Neutral

White

Hot

Red, Blue, Black (Phase C, Hi-Leg)

Table 1

Diagram 1

 • SPD de-energized
 • SPD energized with fault

 • SPD  energized
 • Status=OK 

(LED indicators ALL Green)

ALARM CONDITIONS - CONTACT STATUS

NC

COM

NO

NC

COM

NO

Отзывы: