9.8. FLUE AND BAROMETRIC DRAFT CONTROL CONNECTION
Before connecting the stove pipe, make sure you have removed any accessory from the flue
pipe such as the scraper, shovel, and the poker.
The flue outlet on the Max Caddy furnace is 6" in diameter and the wood only or wood/electric models may be installed
with a 6" chimney approved for use with wood burning heating appliances (2100°F). However, it is mandatory to use a
7" diameter chimney if the retrofit to a wood/oil configuration is probable. In that case, a 6" to 7" reducer must be
installed at the flue outlet of the furnace. If the draft exceeds 0.06 IN.W.C., a barometric control must installed.
Never
install a manual damper.
Secure the exhaust pipe to the flue adapter with three screws.
WOOD ONLY
Diameter 6"
WOOD/OIL
Reducer 7" to 6"
Diameter 7"
Unit oil
Max Caddy pipe
For a proper installation, follow the advice below:
All the exhaust pipe joints must be secured with three screws.
Make sure that each screw goes through the inner wall of both connectors (male and female). See pictures below
showing a male-female coupling.
A minimum rise of ¼" per horizontal foot must be respected.
PROPER INSTALLATION
IMPROPER INSTALLATION
CAUSES RESTRICTION
FLUE
ADAPTER
OIL UNIT’S
UTLET
Содержание MAX CADDY PF01102
Страница 10: ...10...
Страница 47: ...47 15 GENERAL ELECTRICAL DIAGRAM...
Страница 48: ...48 16 ELECTRICAL DIAGRAM FOR PARALLEL FURNACE...
Страница 49: ...49 17 ELECTRICAL DIAGRAM FOR ELECTRIC UNIT...
Страница 55: ...55 22 7 DIFFERENT INSTALLATION...
Страница 61: ...61 26 ELECTRICAL DIAGRAM BECKETT OIL UNIT...
Страница 62: ...62 27 ELECTRICAL DIAGRAM RIELLO OIL UNIT...
Страница 64: ...64 28 4 24V ADDITIONNAL EQUIPMENT 28 5 AIR CONDITIONNING DAMPER 28 6 HUMIDIFIER...
Страница 65: ...65 28 7 HEAT PUMP 29 EXPLODED VIEW AND PART LIST...
Страница 66: ...66...
Страница 67: ...67...
Страница 68: ...68...
Страница 69: ...69...
Страница 70: ...70...
Страница 71: ...71...
Страница 72: ...72...