background image

 

 

Installation Instructions for CW & CW-LSOH Glands

 

42508-01 

Issue 3

 

EC 5909 

 

 

Prysmian Cables & Systems Limited, Components Unit, 

Registered Office

 

Oak Road, Wrexham Industrial Estate, 

Chickenhall Lane, Eastleigh

 

WREXHAM, LL13 9PH, UK 

Hampshire SO50 6YU

 

 

Registered in England 

A Company certified to ISO 9001 and ISO 14001

 

Number 958507 

 

 

Key : 

1.

 

Gland body 

2.

 

Armour clamping ring 

3.

 

Gland barrel 

4.

 

Outer seal 

5.

 

Skid washer 

6.

 

Gland nut 

Not Shown: 

 

Shroud 

 

Earth tag 

 

Lock nut 

 

Equipment Seal (optional

)

Design Ref.  

419CW- 
KA419- 
422LSF- 

Size 

Under Armour 

Ø mm (Max) 

Overall Ø mm 

Armour Wire 

Ø mm 

Length 

X’

 mm 

Exposed 

armour length 

‘Y’

 mm 

Tightening 

Torque 

Z’

 Nm 

Min 

Max 

51  

M16  

8.6 

8.0 

13.2 

0.9 

13 

19.0 

20 

71   M20ss  

8.6 

8.0 

13.2 

0.9 

13 

19.0 

20 

52  

M20s  

11.6 

8.0 

15.8 

0.9 / 1.25  

13 

19.0 

25 

53  

M20  

13.9 

12.9 

20.8 

0.9 / 1.26 

13 

20.0 

30 

55  

M25  

19.9 

17.0 

27.2 

1.25 / 1.6  

15 

22.0 

40 

56  

M32  

26.2 

23.5 

33.5 

1.6 / 2.0  

18 

25.0 

50 

57  

M40  

32.1 

29.0 

39.9 

1.6 / 2.0  

17 

28.0 

65 

59  

M50  

44.0 

39.5 

52.6 

2.0 / 2.5  

24 

32.0 

90 

61  

M63  

55.9 

51.3 

65.3 

2.5 

21 

35.0 

150 

63  

M75  

67.9 

62.5 

78.0 

2.5 

29 

35.0 

150 

Cable Preparation 

1.

 

Place cable alongside the enclosure and allow sufficient length for spreading and terminating the core(s) to the terminals, then 
cut off any surplus cable. 

2.

 

If a shroud is required, slide it onto the cable before proceeding with cable stripping. 

3.

 

Mark the point where the cable passes through the enclosure wall then measure back the length 

‘X’

 and mark position 

‘A’ 

on 

the cable

.

 

4.

 

Cut through over-sheath at position ‘

A’

 using a hacksaw or rotary cutter ensuring that the cut is perpendicular to the cable axis, 

then continue to cut half way through the armour wires. Remove the over-sheath up to the armour wire cut position ‘

A’

 and 

remove the armours by bending back and forth until they snap off. 

5.

 

Using the ‘

Y

’ dimension, mark position ‘

B’ 

and cut and remove the cable over-sheath exposing the armour wires. 

 

Gland Assembly 
1.

 

Dis-assemble the gland noting all the components and orientations as shown above. 

2.

 

Slide the outer sealing components onto the cable. nut (6), skid(5), seal(4) and barrel (3)   

3.

 

Slide the armour clamping ring (2) over the armours - narrow end first.   

4.

 

Slightly raise the armour wires and then slide the Gland body (1) along the cable so that the armour cone sits beneath the 
armours. Spread the armour wires evenly around the cone. 

5.

 

Whilst holding the gland body (1) in place, screw the gland barrel (3) onto the gland body forcing the clamping ring (2) over the 
armour wires and tighten to torque 

‘Z’

. The gland barrel (3) can be unscrewed to check the armour lock and armour continuity. 

6.

 

Replace the gland barrel (3) and tighten up. Then screw the outer nut (6) onto the gland barrel (3) to compress the outer seal 
onto the cable outer sheath.   

Отзывы: