PRULITE.COM 213.746.0360
Prudential Ltg. reserves the right to change design specifications or materials without notice. Please visit prulite.com for most current data.
© 2015 All rights reserved – All products manufactured at: Prudential Ltg. 1774 E. 21st Street, Los Angeles, CA 90058
WARNING:
Ground fixture in accordance with local and national electrical codes. Failure to do so may result in serious personal injury.
6
4 of
LED
Bionic
| Recessed Linear
4˝ Slot
I N S T A L L A T I O N I N S T R U C T I O N S
CO N T IN U O U S R U N X 3, X 7
C 8 I : C O R N E R S I N S T A L L A T I O N
2)
3)
1)
INSTALL ADJACENT SEC TIONS:
Continue installing straight sections
from the corner moving outward
according to row layouts in job drawing.
Pull sections together with aligner
joiner brackets, and secure to studs.
Pull electrical power into fixture.
Confirm spacing at ends
of rows, ensuring that
there is enough room for
installation of finish trim.
INSTALL DRY WALL:
Install drywall, leaving a 5-1/8˝
opening for trim.
INSTALL C8I CORNER:
After removing reflectors and LED trays
but leaving shipping straps, install C8
corner in a wall with a 51/8˝ stud clearance.
Secure with screws through back of corner
into blocking between studs (by others).
MINIMUM DISTANCES:
X3 Light Pocket = 3/4˝
X7 Light Pocket = 11/2˝
Wall-to-Wall = 1/2˝
5-1/8˝
5-1/8˝
4-11/16˝
Ceiling Fixture
C8I Corner
Wall Fixture
DRY WALL
DRY WALL
5-1/8˝
4-11/16˝
ALIGNER
JOINER
BRACKET
Studs
Studs
5-1/8˝
5-1/8˝
BLOCKING
07-02-2020