Proval A240 NAMUR Скачать руководство пользователя страница 1

Operation & Maintenance Manual of A240 NAMUR Solenoid Valves 

1. Description

PROVAL A240 NAMUR Type Solenoid valves are designed for use on double and single acting pneumatic valve actuators  with 

compressed air or non-corrosive and non flammable gases. Please keep this manual for your future reference and maintenance.

2. Areas of Application

PROVAL A240 NAMUR Solenoid valves can be used on Standard industrial applications 

as well as in explosive atmospheres with gases or combustable dust of the category 2 

Group II according to EN 13463-1 only if  suitableexplosion proof coil (magnet) is used. 

This manual only refers to valve body and does not cover the coil (magnet). Please refer 

to coil (magnet) manufacturers application details. In case of use of explosion proof 

coils,  due to thickness of coil an extension adaptor plate is required to be used between 

the valve and the actuator.

Figure-1 : Label of Solenoid Valves

3. Main Parts & Dimensions

In order to avoid any failure, the solenoid valves must be 

installed and initiated by skilled persons. Please read carefully 

the below instructions and follow up the steps carefully.

•  Verify that the valve is correctly chosen for your application

•  Please take appropriate measures to avoid accidental activation

and improper external influence

•  Consider the manual of the magnet coil manufacturer for the 

electrical initiation

•  Protect the equipment and cables from any damage 

•  Avoid static charging or peripheral devices

•  Ensure that the equipment will be available for regular cleaning

•  Avoid strong bending of air tubes  

Coil 
Nut

 
O-Ring

Coil With Connector

Explossion Proof
Coil (magnet)

Functional
Sealing

Valve
Body

1/4"

G/NPT 

Main

Air 

Inlet

(Port.1)

1/4"

G/NPT 

Exhaust

Port

(Port.3)

1/4"

G/NPT 

Exhaust

Port

(Port.5)

Manual

Override

All ports must remain open. The solenoid valve will not be able to operate if any unused ports are clsoed. 

Use only suitable silencers / speed reducers to avoid dirt coming inside the valve.

During the functioning of the valve the magnet coil is heating-up. In order to avoid burning do not touch 

the coils while operating.