Settings
–
Phase Break
:
Parameter
Description
Range
Factory value
Unit
Enable
Phase break function activated
Yes or No
No
-
Low Level
Max nivå för förlorad fas och summaström
Max current for lost phase and residual current
0.1..1000.0
5.0
A
High Level
Min current level for healthy phases
0.1..1000.0
20.0
A
Delay
Time delay between
START
and
TRIP
0..10 000
5 000
ms
Trip relay
TRIP
output relay
0..8
0 (non)
-
Relay pulse
Pulse length of
TRIP
output signal
100..10 000
500
ms
8.6.1 Auto reclosing
– OPTION
Auto reclosing (AR -
RECL
) means that a delayed switch-on is ordered after an initial
TRIP
has been issued
by any of the Overcurrent or Earth fault Protrol protection functions. This option can be acquired for one
bay only, or for all three bays.
Activation of the function can be made at the device using a binary input, or the ACN button. It can also be
ordered by the remote control centre. The ACN button must be pressed 5 s before toggling takes place.
Indication to and order from SCADA is configured as double point / double command, see
I/O-addressing/Binary inputs/Detector m/RECL OFF/ON
and
I/O-addressing/Binary outputs/Detector m/
RECL OFF/ON,
respectively. These objects are blocked from factory.
Visual indication of AR OFF/ON can be chosen as follows:
AR for Detector 1
–
outputs 1
–
8, however, always AUX-LED
AR for Detector 2 and 3
–
outputs 1
–
8, and/or AUX-LED
After reclosure the function is always OFF. Reactivation can be done from SCADA but will always be done
automatically by Acknowledge after a preset time or by pressing the ACN button. Also, a restart of the
device inactivates AR. Manual switch-on of the circuit breaker blocks auto reclosure for 60 s.
The event log shows events for AR OFF/ON, AR startad and AR executed:
RECL OFF
,
RECL ON
,
RECL Started
,
RECL Executed
.
Settings
–
Auto reclosing
:
Parameter
Description
Range
Factory value
Unit
Enable
Choice of function that starts auto reclosing
Disabled/
OC/EF/OC&EF
Disabled
-
Delay
Time delay for auto reclosing
500..60 000
30 000
ms
Reclosure relay
Output relay for reclosing (
ON
output)
0..8
0 (None)
-
Relay pulse
Pulse length of
ON
output signal
100..10 000
500
ms
Input ON/OFF
Input for local activation of auto reclosing
ACN, 1..16
ACN
-
Output indication
Output or LED for local indication OFF/ON
1..8, AUX LED
AUX LED
-
It is strongly recommended to use the Non-directional earth fault function with activation after switch-on
to ensure safe detection of a permanent earth fault after the auto reclosure operation.