Settings
–
Overcurrent
:
Parameter
Description
Range
Factory value
Unit
Enable
Overcurrent steps activated
Disabled
Definite
Standard inv
Very inv
Extremely inv
Long inv
Disabled
-
Level 1
Overcurrent level step 1
0..10 000.0
500.0
A
Delay 1
Time delay between
START
and
TRIP
step 1
0..10 000
40
ms
TMS 1
Time multiplier at inverse time step 1
0.05..1.00
0.05
-
Level 2
Overcurrent level step 2
0..10 000.0
10 000.0
A
Delay 2
Time delay between
START
and
TRIP
step 2
0..10 000
10 000
ms
Event delay
Time delay for
TRIP
interlocked with input
0..25 000
0
ms
Input qualifier
Input for release of
TRIP
0..16
0 (non)
-
Trip relay
TRIP output relay
0..8
0 (non)
-
Relay pulse
Pulse length of
TRIP
output signal
100..10 000
500
ms
Level 1 - set point
address
1
Address for
Set point command
in accordance
with IEC 60870-5-101/-104
0..16 777 214
0
-
Delay 1 - set point
address
Address för
Set point command
in accordance
with IEC 60870-5-101/-104
0..16 777 214
0
-
8.5.2 Earth Fault, General
The IPC402x devices have two types of earth fault detectors; Protrol's patented method, and a
complementary non-directional earth fault function that can be employed when switching onto faults. The
non-directional function can also be used to detect fault connection, that a phase is missing or that one
phase is connected with the wrong polarity. Both methods work independently of each other. Both will set
the indication earth fault
START
.
8.5.3 Earth Fault Protrol
IPC402x initially triggers a ground fault detection sequence on a change in the zero-sequence system. The
current
Level
corresponds to the zero-sequence current measured by the detector.
A
START
signal is generated if the detector reaches State 5, according to Section 8.2. Ground fault
TRIP
is
generated after set time
Delay
or if immediately without delay if the reignition timer has been started by a
previous transient. If the setting
Input qualifier
is selected to any input, 1-16, no TRIP output signal and
message to remote control will be created until there is voltage on the selected input within set time,
Event
delay
. However, the internal event is always generated.