7.5 Analog Inputs (I/O-addressing
– Analog Inputs)
Settings for all analog inputs can be found in the
Config - I / O addressing - Analog Inputs
subtabs:
The
Internal
tab contains internal analogue system signals.
Detector m
lists analog signals from the detector functions.
All analog signals have the same setting options. Below is a general description.
For more information on each individual item, see the following tab descriptions.
Parameter
Description
Range
Unit
Description
Brief descriptive name for the object.
-
-
Type
Type of analogue object;
Different formats and scaling.
1
Normalized [0
–100 %],
Normalized [0
–120 %],
Floating point [SI],
Scaled [SI*1],
Scaled [SI*10],
Scaled [SI*100]
-
Settings
– Blocked
The signal is blocked, i.e. no value / status is sent
to the remote end.
Also applies to "interrogation" (status request).
Yes or No
-
Settings
– Timetagged
The signal is timestamped upon change. The time
is also sent to the remote end.
Yes or No
-
Settings
– Cyclic
The signal is sent using cyclic transmission
Yes or No
-
Deadband [%]
Deadband - indicates how much change is
needed for a new value to be sent to the remote
end.
1)
%
Address 8
Upper octet of the address. Decimal.
0 … 255
-
Address 16
Lower octets of the address. Decimal.
0 … 65 535
-
1
For a detailed description of what the different types provide regarding format, scaling and how the deadband is
defined, see descriptions in the following text.