7.3.1 Binary Inputs
– Input 1-16/22/37
1
Settings for binary objects connected to physical inputs on the device, ACN button and IRF.
Limitation of events from binary inputs that change status frequently can be made using the parameter
Delay
, see description in the table on the previous page.
Only specific settings and differences to the normal are described below. See chapter 7.3 for a general
description of the various configuration options.
The objects have the following factory settings:
▪
Type
-
Single point
▪
Settings
–
Blocked
- No
▪
Settings
–
Negative
- No
▪
Settings
–
Time tagged
- Yes
▪
Delay
- 0 ms
Settings
–
Input 1-16/22/37
:
Parameter
Description
Factory value
address lower octets
2
Ack button
Object linked to the ACN button on the front panel.
Can only have the type
single indication
.
100
Input n
Object connected to physical inputs
n
(
n
= 1-15).
100+
n
Input 16
Object connected to physical input 16.
Can only have the type
single indication
.
116
Input 16 + n
Object connected to physical inputs 16 +
n
(
n
= 1-5).
150+
n
Input 22
Object connected to physical input 22.
Can only have the type
single indication
.
122
Input 22 + n
Object connected to physical inputs 22 +
n
(
n
= 1-14).
160+
n
Input 37
Object connected to physical input 37.
Can only have the type
single indication
.
175
IRF
Indication for internal error.
Can only have the type
single indication
.
117
1
If the device is an IPC4020exp4 or IPC4020exp6, there are additional physical binary inputs available.
2
Övre oktetten är alltid 0 som fabriksvärde.