DEL2091 Issue 4 02/11 SB
Page 1 of 3
Copyright © Protec Fire Detection plc 2010
6000
PLUS
/HT/TSL Installation, Commissioning and Service Instructions
Overview
The Protec 6000
PLUS
/HT/TSL is a loop powered fire sensor which reports back thermal levels in its installed location to the fire
alarm control panel. The sensor is also equipped with an integrated loop powered programmable electronic sounder with
speech messages, beacon and an integrated loop isolator.
Technical Specification
Loop protocol
Protec Algo-tec™ 6000
PLUS
Loop isolator fitted
Yes
Loop voltage range
18 to 27V Algo-tec™ Protocol
Loop average quiescent current (24V loop)
0.4mA
Loop average alarm current (24V loop)
13mA
Analogue values
Thermal
Normal 80 to 180 bits
Fault Low <25 bits
Fault High>250 bits
Indications
On-board red indicating LED
Environmental operational limits
-10 to 50 degrees C ( 95% RH no condensation or icing )
Sounder Frequencies
Continuous 990Hz, Warble 730Hz to 990Hz, Bell 800Hz
Sounder synchronisation
Synchronised automatically by the control panel.
IP rating
IP21C
Isolator Specification
Please see Protec DEL2110 for details
Installation
1. Base options: 6000PLUS/BASE
LPCB Approved as part of product approval
6000PLUS/FFBASE
LPCB Approved as part of product approval
28-075-01 (Plug and Play Fast Fix)
LPCB Approved as part of product approval
28-075-02 (Plug and Play Surface)
LPCB Approved as part of product approval
Note: See individual information sheets for base wiring details.
2. Install the detector in the base, turn firmly clockwise.
Commissioning
1. Each 6000
PLUS
detector has a unique serial number which will be used as part of the commissioning of the fire alarm
system. It is necessary to remove one of the ‘peelable’ bar code labels present on the product and place it in the
commissioning booklet supplied with each Protec addressable control panel. The bar code sticker should be placed at the
relevant loop and address position intended. It is important that serial numbers are not mixed otherwise the addressing of
the 6000
PLUS
/HT/TSL will be incorrect when commissioned.
2. Commission the device onto the system as detailed in the installation and commissioning manual for the fire alarm panel
being used.
6000
PLUS
/HT/TSL Certification Details
EN Standards Compliance/ Approvals table
0 8 3 2
Protec Fire Detection plc, Nelson, Lancashire, England, BB9 6RT
10
0832-CPD-1184
EN 54 - 3:2001 + A1 + A2
Alarm devices – Sounder/Voice Sounder
Type A: For indoor use
6000PLUS/HT/TSL
EN 54 - 5
Point type Heat detector
Class A1/A2
6000PLUS/HT/TSL
EN 54 - 17: 2005
Short-circuit isolator
6000PLUS/HT/TSL
Technical Data included in this datasheet DEL2091 Issue 4
High Sensitivity
Med Sensitivity
Low Sensitivity
Isolator/sounder
Approved to:
EN 54 - 5: 2000 + A1:
2002
Class A1
Approved to:
EN 54 - 5: 2000 + A1: 2002,
Class A2
Not approved.
Equivalent to EN 54-5: 2000 +
A1: 2002 Class B
Approved to: EN 54-17: 2005
EN 54 - 3: 2001 + A1: 2002 + A2: 2006
**See note below on EN54 approved
talking sounder message