background image

                       

 

DEL2091 Issue 4 02/11  SB   

 

                 Page 1 of 3 

                             Copyright © Protec Fire Detection plc 2010

 

    

6000

PLUS

/HT/TSL Installation, Commissioning and Service Instructions

 

Overview

 

The Protec 6000

PLUS

/HT/TSL is a loop powered fire sensor which reports back thermal levels in its installed location to the fire 

alarm  control  panel.  The  sensor  is  also  equipped  with  an  integrated  loop  powered  programmable  electronic  sounder  with 
speech messages, beacon and an integrated loop isolator. 

 

Technical Specification

    

 

Loop protocol 

Protec Algo-tec™ 6000

PLUS

 

Loop isolator fitted 

Yes 

Loop voltage range 

18 to 27V Algo-tec™ Protocol 

Loop average quiescent current (24V loop) 

0.4mA 

Loop average alarm current (24V loop) 

13mA 

Analogue values 

Thermal 

Normal 80 to 180 bits 
Fault Low <25 bits 
Fault  High>250 bits 

Indications 

On-board red indicating LED  

Environmental operational limits 

-10 to 50 degrees C ( 95% RH no condensation or icing ) 

Sounder Frequencies 

Continuous 990Hz, Warble 730Hz to 990Hz, Bell 800Hz 

Sounder synchronisation 

Synchronised automatically by the control panel. 

IP rating 

IP21C 

Isolator Specification 

Please see Protec DEL2110 for details  

 

Installation 

1.  Base options: 6000PLUS/BASE  

 

 

LPCB Approved as part of product approval 

 

6000PLUS/FFBASE 

 

 

LPCB Approved as part of product approval 

 

 

28-075-01 (Plug and Play Fast Fix)   

LPCB Approved as part of product approval 

28-075-02 (Plug and Play Surface)   

LPCB Approved as part of product approval 

Note: See individual information sheets for base wiring details.

 

2.  Install the detector in the base, turn firmly clockwise. 

 

Commissioning 

1.  Each  6000

PLUS

  detector  has  a  unique  serial  number  which  will  be  used  as  part  of  the  commissioning  of  the  fire  alarm 

system.  It  is  necessary  to  remove  one  of  the  ‘peelable’  bar  code  labels  present  on  the  product  and  place  it  in  the 
commissioning booklet supplied with each Protec addressable control panel.  The bar code sticker should be placed at the 
relevant loop and address position intended. It is important that serial numbers are not mixed otherwise the addressing of 
the 6000

PLUS

/HT/TSL will be incorrect when commissioned. 

 

2.  Commission  the device  onto  the  system as detailed  in  the installation and commissioning  manual for  the  fire  alarm panel 

being used.  

 

6000

PLUS

/HT/TSL Certification Details 

EN Standards Compliance/ Approvals table 

 

 
 

0 8 3 2 

Protec Fire Detection plc, Nelson, Lancashire, England, BB9 6RT 

10 

0832-CPD-1184

 

EN 54 - 3:2001 + A1 + A2 

Alarm devices – Sounder/Voice Sounder 

Type A: For indoor use 

6000PLUS/HT/TSL 

EN 54 - 5 

Point type Heat detector 

Class A1/A2 

6000PLUS/HT/TSL 

EN 54 - 17: 2005 

Short-circuit isolator 

 

6000PLUS/HT/TSL 

Technical Data included in this datasheet DEL2091 Issue 4 

 

High Sensitivity 

Med Sensitivity 

Low Sensitivity 

Isolator/sounder 

Approved to: 
EN 54 - 5: 2000 + A1: 
2002 
Class A1 

Approved to: 
EN 54 - 5: 2000 + A1: 2002, 
Class A2 

Not approved. 
Equivalent to EN 54-5: 2000 + 
A1: 2002 Class B 

Approved to: EN 54-17: 2005 
EN 54 - 3: 2001 + A1: 2002 + A2: 2006 

**See note below on EN54 approved 
talking sounder message

 