background image

                       

 

DEL2083 ISS2 NOV 2011 NH  

Page 1 of 2 

  Copyright © Protec Fire Detection plc 2011 

6000CCO Installation and Commissioning Instructions

 

Overview

 

 

The Protec Clean Contact Interface ( CCO ) is a loop powered output device providing a set of volt free changover contacts. The 
contacts may be used to connect Protec addressable loops to any form of ancillary equipment. 

 

Technical Specification

 

Loop protocol 

Protec Algo-tec™ 6000 

Loop isolator fitted 

Yes, on board 

Loop voltage range 

16 to 28V peak loop 

Loop quiescent current (24V peak loop) 

0

.

6mA 

Loop alarm current ( maximum ) 

19mA 

Clean contact output details 

Single pole changeover rated for 1A maximum at 24V DC 

Indications 

On-board red indicating LED  

Environmental operational limits 

0 to 50 degrees C ( 95% RH no condensation or icing ) 

Loop isolator specification 

Please consult Protec DEL2110 for details 

 

Installation 

1. 

Ensure tests are carried out on the cable using a 500V DC insulation tester ( Megger

TM 

). The readings between each cable 

core, and each core and earth ( screen ) should be greater than 10M

Ensure that all cabling is completely discharged 

before connecting to the 6000/CCO. 

 
2.  Connect the cabling as follows; 

The incoming series 6000 loop must be connected to the terminals marked LOOP+ and LOOP- 
The outgoing series 6000 loop must be connected to the remaining LOOP+ and LOOP- terminals 
All screen wiring must be securely terminated to a local earth point within the back-box.  

 
3.  To comply with the impact, shock and ESD requirements of EN54 parts 17 and 18, the interface must be mounted securely 

on a DIN rail which in turn is securely fastened using suitable metal screws or metal nuts and bolts within a plastic or metal 
enclosure whose dimensions are at least 100mm x 90mm x 50mm and which has a minimum ingress protection rating of 
IP20.  A minimum wall thickness of 1.0 mm for metal enclosures and 1.5 mm for plastic enclosures is required. 

 

 
 

Commissioning

 

1.  Each 6000/CCO has a unique serial number which will be used as part of the commissioning of the fire alarm system. It is 

necessary to remove one of the ‘ peelable ’ bar code labels present on the product and place it in the commissioning booklet 
supplied with each Protec addressable control panel.  The bar code sticker should be placed at the relevant loop and 
address position intended for the 6000/CCO. It is important that serial numbers are not mixed otherwise the addressing of 
the 6000/CCO will be incorrect when commissioned. 

 
2.  Commission the device onto the system as detailed in the installation and commissioning manual for the fire alarm panel 

being used. 

 
 

6000/CCO Certification Details 
 

 

 
 
 

0 8 3 2 

 

Protec Fire Detection plc, Nelson, Lancs 

11 

0832-CPD-1162 

 

EN54 – 17 : 2005 

Short Circuit Isolator 
 
6000/CCO 
Technical Data included 
in this datasheet 

 

EN54 – 18 : 2005 

Input / Output Devices 
 
6000/CCO 
Technical Data included 
in this datasheet

 

 