    6000

PLUS

/OPHTCO/S Installation, Commissioning and Service Instructions

 

Overview 

The Protec 6000

PLUS

/OPHTCO/S is a loop powered Fire sensor which reports Smoke, Thermal and Carbon Monoxide levels 

in its installed location to the fire alarm control panel. The sensor is also equipped with an integrated loop powered sounder. 

 

Technical Specification

    

 

Loop protocol 

Protec Algo-tec™ 6000

PLUS

 

Loop isolator fitted 

Yes 

Loop voltage range 

18 to 27V Algo-tec™  loop 

Loop average quiescent current (24V loop) 

0

.

45 mA 

Loop average alarm current (24V loop ) 

5mA 

Analogue values 

Smoke 

Thermal 

Carbon Monoxide 

Normal 40 to 60 bits 
Fault Low <35 bits 
Fault low High>90 bits 

Normal 80 to 180 bits 
Fault Low <25 bits 
Fault  High>250 bits 

Normal 30 to 100 bits 
Fault Low <20 bits 
Fault  High>150 bits 

Indications 

On-board red indicating LED  

Environmental operational limits 

-10 to 50 degrees C ( 95% RH no condensation or icing ) 

Sounder Frequencies 

Continuous 990Hz, Warble 730Hz to 990Hz, Pip 990Hz 

Sounder synchronisation 

Sounder synchronisation is achieved by panel control 

IP rating 

IP21C 

Isolator Specification 

Please see Protec DEL2110 for details  

 
Installation 

1.  Base options: 6000PLUS/BASE  

 

 

LPCB Approved as part of product approval 

6000PLUS/FFBASE 

 

 

LPCB Approved as part of product approval 

28-075-01 (Plug and Play Fast Fix)   

LPCB Approved as part of product approval   

28-075-02 (Plug and Play Surface)   

LPCB Approved as part of product approval 

Note: See individual information sheets for base wiring details.

 

2.  Install the detector in the base, turn firmly clockwise. 

 

Commissioning 

1.  Each  6000

PLUS

/  detector  has  a  unique  serial  number  which  will  be  used  as  part  of  the  commissioning  of  the  fire  alarm 

system.  It  is  necessary  to  remove  one  of  the  ‘peelable’  bar  code  labels  present  on  the  product  and  place  it  in  the 
commissioning booklet supplied with each Protec addressable control panel.  The bar code sticker should be placed at the 
relevant loop and address position intended. It is important that serial numbers are not mixed otherwise the addressing of 
the 6000PLUS/OPHTCO/S will be incorrect when commissioned. 

 

2. 

Commission  the device  onto  the  system as  detailed  in  the installation and commissioning  manual  for  the  fire  alarm  panel 
being used. 

 

 

6000

PLUS

/OPHTCO/S Certification Details

 

EN Standards Compliance/ Approvals table 

 
 
 
 

0 8 3 2 

Protec Fire Detection plc, Nelson, Lancashire, England, BB9 6RT 

10 

0832-CPD-1177

 

EN 54 - 5 

Point type heat detector 

Class A2 

6000

PLUS

/OPHTCO/S 

EN 54 - 7 

Point type smoke detector 

 

6000

PLUS

/OPHTCO/S 

EN 54 - 3: 2001 + A1 + A2 

Alarm devices – Sounder 

Type A: For indoor use 

6000

PLUS

/OPHTCO/S 

EN 54 - 17:2005 

Short-circuit isolator 

 

6000

PLUS

/OPHTCO/S 

Technical Data included in this datasheet DEL2104 Issue 4 

 

High Sensitivity 

Med Sensitivity 

Low Sensitivity 

Isolator/sounder 

No Approval 

Approved to:  
EN 54-7: 2000 + A1: 2002 + A2: 2006 
EN 54-5: 2000 + A1: 2002, Class A2 
CEA 4021:2003-07 

Approved to: 
EN 54-7: 2000 + A1: 2002 + A2: 2006 
EN 54-5: 2000 + A1: 2002, Class A2 
CEA 4021:2003-07 

Approved to: 
EN 54-17: 2005 
EN 54-3: 2001 + A1: 2002 + A2: 
2006 