Connecting the Device to the PC
The 6000/LOOP/REPEATER must be completely disconnected from the loop and removed from the
back box before it can be updated. When removing the device from the back box, make sure the loop
continuity switch is set to the commissioning position to maintain the loop continuity.
Connect the USB cable to the PC
Using a small terminal screwdriver (e.g. 2.5mm), gently push and hold on the programming
switch through the area marked on the product label
Connect the Micro-USB cable to the device
Release the terminal screwdriver
If the connection is successful the device will appear blank (indicators and LCD not illuminated)
Ensure the device is
disconnected from the loop.