Reference MVI56-CAS
♦
ControlLogix Platform
Teledyne CA Slave Module
ProSoft Technology, Inc.
Page 67 of 86
December 26, 2007
5.6.2 Port
2
Group Register
Content
Description
5040
Enabled
This parameter enables the port. Valid entries are 0 and 1.
5041
Baud
Rate
This is the baud rate to be used on the port. Enter the
baud rate as a value. For example, to select 19K baud,
enter 19200. Valid entries for this field include 110, 150,
300, 600, 1200, 2400, 4800, 9600, 19200, 28800, 38400,
57600, and 115.
5042
Parity
This is the parity code to be used for the port. None, Odd,
Even.
5043
Data
Bits
This parameter sets the number of data bits for each word
used by the protocol. Valid entries are 5 or 8.
5044
Stop
Bits
This parameter sets the number of stop bits to be used
with each data value set. Valid entries are 1 and 2.
5045
RTS
On
This parameter sets the number of milliseconds to delay
after RTS is asserted before the data is transmitted. Valid
values are 0 to 65535.
5046
RTS
Off
This parameter sets the number of milliseconds to delay
after the last byte of data is sent before the RTS modem
signal will be set low. Valid values are 0 to 65535.
5047
Minimum
Response
Time
This parameter specifies the minimum number of
milliseconds to delay before responding to a request
message. This pre-send delay is applied before the RTS
on time. This may be required when communicating with
slow devices.
5048
Use CTS
Line
This parameter specifies if the CTS modem control line is
to be used. If the parameter is set to 0, the CTS line will
not be monitored. If the parameter is set to 1, the CTS line
will be monitored and must be high before the module will
send data. This parameter is normally only required when
half-duplex modems are used for communication (2-wire).
5049
Slave
ID
This parameter defines the virtual slave address for the
internal database. Any request received by the port with
this address will be processed by the module. Be certain
each device has a unique address on a network. Valid
range for this parameter is 1 to 255 (247 on some
networks).
5050
Use Guard
Band
Not implemented.
5051
Guard
Band Time
Not implemented.
5052
Direct
Control
This parameter enables direct control. If enabled, a Select
command is not required before a Control command.
Valid entries are 0 and 1.
5053
Swap
Config
This parameter sets data swapping. The swapping is set
as a bit field. Bit 0 corresponds to status data, Bit 1 to
analog data, and Bit 2 to meter data.