Reference MVI56-CAS
♦
ControlLogix Platform
Teledyne CA Slave Module
ProSoft Technology, Inc.
Page 65 of 86
December 26, 2007
Offset Content
Description
235
Port 1 Status Scan
Contains the port's scan status in the upper byte and
the port's current error status in the lower byte. The
scan status is encoded in the upper byte as follows:
Bit 13 - Status Data Scan
Bit 14 - Analog Data Scan
Bit 15 - Read All Data Scan
236
Port 2 Status Scan
Contains the port's scan status in the upper byte and
the port's current error status in the lower byte. The
scan status is encoded in the upper byte as follows:
Bit 13 - Status Data Scan
Bit 14 - Analog Data Scan
Bit 15 - Read All Data Scan
5.6 MVI56-CAS
Configuration Data Definition
This section contains listings of the MVI56-CAS module's database that are
related to the module's configuration. This data is available to any node on the
network and is read from the ControlLogix processor when the module first
initializes.
5.6.1 Port
1
Group Register
Content
Description
Backplane
Setup
5000
Status
Length
This parameter specifies the number of status words in
the module (0 to 250).
5001
Analog
Length
This parameter specifies the number of analog words in
the module (0 to 250).
5002
Meter
Length
This parameter specifies the number of meter words in the
module (0 to 250).
5003
Tank
Length
This parameter specifies the number of tank words in the
module (0 to 250).
5004
Backplane
Fail
This parameter specifies the number of successive
transfer errors that must occur before the communication
ports are shut down. If the parameter is set to zero, the
communication ports will continue to operate under all
conditions. If the value is set to larger than zero (1 to
65535), communications will cease if the specified number
of failures occur.
5005
Spare
Spare
5006
Spare
Spare
5007
Spare
Spare
5008
Spare
Spare
5009
Spare
Spare
5010
Enabled
This parameter enables the port. Valid values are 0 and 1.