5.1.3 Hardware
Specifications
Specification
Description
Backplane Current Load
800 mA @ 5 V DC; 3mA @ 24V DC
Operating Temperature
0 to 60°C (32 to 140°F)
Storage Temperature
-40 to 85°C (-40 to 185°F)
Shock 30g
Operational
50g non-operational
Vibration: 5 g from 10 to 150 Hz
Relative Humidity
5% to 95% (non-condensing)
LED Indicators
Module Status
Backplane Transfer Status
Application Status
Serial Activity
Debug/Configuration port (CFG)
CFG Port (CFG)
RJ45 (DB-9M with supplied cable)
RS-232 only
Application ports (PRT1 & PRT2)
Full hardware handshaking control, providing radio, modem and multi-drop support
Software configurable
communication parameters
Baud rate: 110 to 115,200 baud, depending on protocol
RS-232 and 422
Parity: none, odd or even
Data bits: 5, 6, 7, or 8
Stop bits: 1 or 2
RTS on/off delay: 0 to 65535 milliseconds
App Ports (P1,P2) (Serial modules)
RJ45 (DB-9M with supplied cable)
RS-232 handshaking configurable
500V Optical isolation from backplane
Shipped with Unit
RJ45 to DB-9M cables for each port
6-foot RS-232 configuration cable
5.1.4 Functional
Specifications
Function
codes
o
1: Read output data
o
2: Read analog data
o
3: Read meter data
o
10: Read frozen analog values
o
11: Read frozen meter data
o
16: Read all data
o
20: Read tank data from RTU
o
30: Control momentary select
o
31: Control momentary operate
o
32: Control continuous select
o
33: Control continuous operate