2.4 [Module]
This section of the file describes the database setup and module level
parameters.
[Module]
Module Name: MVI46-GEC Communication Module DEFAULT
2.4.1 Module
Name
0 to 80 characters
This parameter assigns a name to the module that can be viewed using the
configuration/debug port. Use this parameter to identify the module and the
configuration file.
2.5 [Server
x]
You can configure up to five servers ([Server 0] through [Server 4]). The
configuration section for each server contains the same set of parameters. You
can configure the parameters for each server to meet the requirements of your
application.
2.5.1 Enabled
Yes or No
This parameter determines if the server will be utilized by the module. If a value
of 'Yes' is entered, the server will be used. Any other value will disable the
server.
2.5.2 Service Port Number
1 to 65535
This parameter sets the TCP/IP service port for this server. Each server can
have its own unique service port or can share the same number with other
servers.
2.5.3 Connection
Timeout
0 or 5000 to 65535
This parameter specifies the number of milliseconds the server will permit the
server to be inactive after a connection is made before closing the socket. This
timeout period is reset on each read or write packet. If the parameter is set to 0,
the connection will not timeout.