7.7
Communication Error Codes
Note: If an error code is reported that is not listed below, check with the documentation of the Modbus
device(s) on the module's application ports. Modbus devices can produce device-specific error codes.
7.7.1 Standard Modbus Protocol Exception Code Errors
Code
Description
1
Illegal Function Code
2
Illegal Data Address
3
Illegal Data Value
4
Failure in Associated Device
5
Acknowledge
6
Busy, Rejected Message
7.7.2 Module Communication Error Codes
Code
Description
-1
CTS modem control line not set before transmit
-2
Timeout while transmitting message
-11
Timeout waiting for response after request
253
Incorrect slave address in response
254
Incorrect function code in response
255
Invalid CRC/LRC value in response
7.7.3 Command List Entry Errors
Code
Description
-41
Invalid enable code
-42
Internal address > maximum address
-43
Invalid node address (< 0 or > 255)
-44
Count parameter set to 0
-45
Invalid function code
-46
Invalid swap code