VTrak 15200 User Manual
136
For information on fan replacement, see .page 180.
Buzzer
From the Enclosure Management menu, press 2 and Enter to access the Buzzer
(Beeper). You can also access the Buzzer from the Main menu.
Buzzer
1. Silence Buzzer
2. Enable Buzzer
R. Return to Previous Menu
Please enter your menu choice>
2
Enable buzzer(y/n)?>
y
Press 2 and Enter to enable or disable the buzzer. Press Y and Enter to confirm.
Press 1 and Enter to silence the buzzer. Press Y and Enter to confirm.
Silence
means to cancel the audible alarm for the current event only. If another
event happens, the buzzer will sound again.
Temperature
From the Enclosure Management menu, press 3 and Enter to access
Temperature.
*********************Temperature********************
Temperature # Celsius Fahrenheit
Normal Operational Range
-------------------------------------------------------------------------------
1
27
80
<= 45 Celsius
2
27
80
<= 45 Celsius
3
24
75
<= 45 Celsius
4
23
73
<= 45 Celsius
5
24
75
<= 45 Celsius
6
38
100
<= 55 Celsius
Press Enter key to return
Look for a temperature measurement above the Normal Operational Range. An
elevated temperature can be the result of a failed fan or blocked cooling
passages. Temperature #6 has a higher range because it is located directly
above the main controller board.
Voltage
From the Enclosure Management menu, press 4 and Enter to access Voltage.