P
Batch
CONTACT
Manual
Analog
Analog
Manual
CONTACT
Batch
Continuous
display
- ANALOG
- MANUAL
- CONTACT
- BATCH
P
B0085
Fig. 11: Selecting the operating mode (MODE menu)
A1796
Fig. 12: [Analog] operating mode settings
1.
Keep the
[P]
key pressed until the display flashes. Then release the
[P]
key
2.
Press the arrow key until
[MODE]
appears on the display. Then
press the
[P]
key
3.
Keep the arrow key pressed until
[ANALOG]
appears on the display.
Then press the
[P]
key
ð
The pump is now operating in Analog mode.
If the red LED display lights up and [ANALG]
appears on the display, then the pump is not
receiving an analog signal.
1.
Keep the
[P]
key pressed until the display flashes. Then release the
[P]
key
2.
Keep the arrow key pressed until
[SET]
appears on the display.
Then press the
[P]
key
3.
Keep the arrow key pressed until
[ANALG]
appears on the display.
Then press the
[P]
key
4.
Keep the arrow key pressed until
[4...20 mA]
appears on the dis‐
play. Then press the
[P]
key
ð
The pump reacts proportionally to the current signal, 4 mA = 0
strokes/min., 20 mA = maximum rate.
5.
Use the START/STOP key to start or stop the pump.
Setting "Analog" operating mode
Setting the analog input 4 ... 20 mA
Setting the additional components
32