NOTICE!
–
Route the overflow and drainage lines with a slope.
These must be operated without back pressure
–
To drain the system install a T-piece with a stopcock to
provide a drainage option between the chamber 3 shut-
off valve and the feed pump
1.
Connect the preparation water line to the water fitting
2.
Connect the concentrate pump line for the liquid polymer
3.
If available: Connect the feed pump (not contained in the scope of
supply) to the extraction line
4.
Connect up the drainage lines and lead into a suitable drain
5.
Connect up the overflow line to the overflow connector and lead into
a suitable drainage
6.3 Installation, electrical
WARNING!
Live parts!
Possible consequence: Fatal or very serious injuries
–
Measure: Always disconnect the system from the mains
power supply at the electrical connections before car‐
rying out any installation work
–
Secure the system to prevent it being switched back on
again
6.3.1 Mains Power Connection
CAUTION!
Danger of malfunction!
Ensure that the terminals are assigned correctly when con‐
necting the units.
Ensure that the motors rotate in the right direction ... when
connecting the stirrers, powder feeders, motor pumps.
1.
Connect the electrical supply cable as shown in the wiring diagram
(see the pouch in the control cabinet
2.
Guide the mains cable through an appropriate opening in the
system control cabinet and connect it in the cabinet to the provided
terminal strip
Assembly and installation
26