6.5.2 The second operating and display level
n
User qualification: trained user
A1204
Warning and safety threshold settings
Wiper control - time interval, manual control
Controller settings - set power and mode
Remote control - pause, analog I/O
Setting times - cooling, disabling lamps, rinse valve
Next
HOME
Menu page 2
Before
Fig. 27: The second operating and display level
6.5.2.1 Warning and safety threshold settings
You can set the warning and safety threshold in this menu, see
also
Chapter 6.3 ‘Adjusting the Dulcodes A control’ on page 20.
The setting for the warning and alarm limit depends on the type of
control selected:
n
The UV sensor signal is monitored in W/m
2
with internal control
by specification of the electrical lamp power. Limits are abso‐
lute values and remain constant when the setpoints change.
n
In the event of control by specification of the UV sensor signal
in W/m², any deviation below the setpoint is monitored as a %.
The limits move as the setpoint changes. The absolute gap
between the setpoint and the limit decreases with smaller set‐
points. If the second stage is selected via the digital contact
input, then the limits are also monitored with the percentage
deviation.
A1205
Menu
Thresholds by power setpoint
Safety threshold:
Warning threshold:
550 W/m
2
500 W/m
2
Home
Fig. 28: [Thresholds by power setpoint] internal
The warning threshold can only be set to be greater than the safety
threshold.
Control
38