11.2.7.4
‘mA Output (Option)’
‘Menu / Information
è
Settings
è
Inputs/Outputs
è
mA output
è
...’
Here you can set which current range is to be used at the mA output.
You can then set whether the current stroke rate (strokes / house) is to be
signalled at the mA output or the capacity (litres / hour) and the corre‐
sponding value for 20 mA.
11.2.7.5
‘Diaphragm Rupture’
‘Menu / Information
è
Settings
è
Inputs/Outputs
è
Diaphragm rupture
è
...’
The setting options for the ‘Diaphragm rupture’ function only
exist if a diaphragm rupture indicator is electrically installed.
The symbol for diaphragm appears .
In the
‘Diaphragm rupture’
sub-menu you can select whether the pump
generates a warning message or a fault message in the event of a dia‐
phragm rupture.
11.2.7.6
‘Flow Control’
‘Menu / Information
è
Settings
è
Inputs/Outputs
è
Flow control
è
...’
The setting options for the ‘Flow control’ function only exists
if a flow control has been electrically installed. The symbol
for flow control appears: .
A dosing monitor, such as a Flow Control (also DulcoFlow
®
), can register
the individual pressure impacts of the pump and report it to the pump.
The pump switches to fault mode if this feedback is missing in a
sequence, as set under
‘Error tolerance’
.
It is possible to switch the function on and off under
‘Activation’
.
It is possible to set whether the function is to be deactivated with auxiliary
frequency under
‘if Auxiliary’
.
11.2.7.7
‘Pause Input’
‘Settings
è
Inputs/Outputs
è
Pause
è
...’
In the
‘Pause’
menu, you can select whether the pump switches to
‘Pause’
with a "normally-open (NO)" or "normally-closed (NC) input con‐
tact signal.
11.2.7.8
‘Level Warning’
‘Settings
è
Inputs/Outputs
è
Level warning
è
...’
Set Up /
‘Menu’
59