Number
Description
Function
P6
Cover CLOSE
P2 ... P7
Internal circuit
P2 ... P7
Water level
reduction
2.4 Delay periods within the system
Function
Delay in seconds (s)
State change of the digital inputs
[Not faulty] to [Faulty]
[Faulty] to [Not faulty]
OPEN ➨ CLOSE
CLOSE ➨ OPEN
Liquid level
10 s
10 s
Water_flow_1
30 s
1 s
Water_flow_2
30 s
1 s
Level --
10 s
60 s
Level -
10 s
10 s
Level +
10 s
10 s
Level ++
10 s
600 s
Cover
[CLOSE]
1 s
1 s
Gutter cleaning
1 s
25 s
JetStream feedback
1 s
1 s
Neck shower feedback
1 s
1 s
Massage pump feedback
1 s
1 s
2.5 Switching of inductive loads
If you connect an inductive load, i.e. a consumer
which uses a coil (e.g. an alpha motorised pump),
then you must protect your controller with a protec‐
tive circuit. If in doubt, consult an electrical techni‐
cian for advice.
The RC member protective circuit is a simple, but nevertheless
very effective, circuit. This circuit is also referred to as a snubber or
Boucherot member. It is primarily used to protect switching con‐
tacts.
Installation of the F module
7