5.2  Backwashing with 5-way valve

WARNING!
Possible consequence: Fatal or very serious inju‐

ries.
Cause: With a 230 V power supply to the Dulco‐

marin

®

 II, 230 V exists at the terminals 

[P2] ... P5

after switching on of the relay.
Measure: Disconnect the system before carrying

out any work on the power supply. By taking suit‐

able measures, ensure that there is no danger for

the entire system arising from the mains voltage at

the terminals 

[P2] ... P5.

The times for the circulation must be set with the 

[F4] > [CONFIG]

[F2] > [OPTION] > [TIMER] . If no times are set, then the circula‐

tion will not run automatically.
To permit automatic backwashing, the 5-way valve (rod valve) (line

1) must be connected to terminal 

[P2] or [P4] of the F module and

230 V then connected. If you are operating two lines in parallel, the

second 5-way valve must be connected to terminal 

[P3] or [P5] of

the F module.

Once you have electrically connected the 5-way valve, then

set the function of the terminals 

[P2] ... P5 in the

[Configuration] operating menu of the Dulcomarin

®

 II.

ð

You can freely select these functions. A free allocation of

all functions to each relay is not universally possible.

Please observe our allocation suggestion in the appendix

of the operating instructions. In the appendix, you can

find a series of the most appropriate application solu‐

tions.

5.3  Hydraulic procedure

5.3.1  First filtrate

So that after backwashing no dirt or contamination can reach the

swimming pool, once the filter bed of the filter returns to the normal

condition, the first filtrate must be disposed of. The first filtrate

valve is activated for a duration of 20 seconds after backwashing.

Use of a 3-way rod valve with water or compressed air as its

working energy is recommended. Terminal allocations can be

made for both first filtrate valves (lines 1 and 2) at the terminals

[P2] ... [P7].

5.3.2  Internal circuit

If a swimming pool roll cover is fitted and a contact is made to the

digital input 

[K1] ... [K5] and activated, then the Dulcomarin

®

 II

switches a valve via the terminals 

[P2] ... [P7] if the roll cover

closes. Consequently either the level in the swimming pool can be

reduced and/or an inlet nozzle can be used as a suction line. This

ensures internal mixing of the water, without significant evaporation

and an open swimming pool.

Dispose of the first filtrate in the drain

Application examples for the F module functions

 

 

 

19

Содержание DULCOMARIN 2

Страница 1: ...l EN Only valid in conjunction with the complete operating instructions for DULCOMARIN II Part number 985358 Version BA DC 086 11 16 EN Please carefully read these operating instructions before use Do...

Страница 2: ...ation Warning information include detailed descriptions of the hazardous situation The following symbols are used to highlight instructions links lists results and other elements in this document Tab...

Страница 3: ...cuit 19 5 3 3 Backflow shut off valve 20 5 4 Lowering the water level 20 5 5 Water flow circulation flow control 21 5 6 Water level control 21 5 6 1 Single stage level function 22 5 6 2 Two level func...

Страница 4: ...flow shut off valve n Lowering of the water level during standby operation n Circulation flow control Flowcontrol n Water level control n Sample water valve n Heating function Heating control heat exc...

Страница 5: ...ol variable circulation circulating pump filtration circuit 2 Iout2 CntrlChlorination Control variable raise chlorine dosing Iout2 Cntrl pH_increase Control variable raise pH value Iout2 Cntrl pH_redu...

Страница 6: ...JetStream on off Switches the JetStream counterflow system K1 K5 Neck shower on off Switches the neck shower on off K1 K5 Massage on off Switches the massage nozzles on off K1 K5 Backwash EM STOP Back...

Страница 7: ...1 s 1 s Gutter cleaning 1 s 25 s JetStream feedback 1 s 1 s Neck shower feedback 1 s 1 s Massage pump feedback 1 s 1 s 2 5 Switching of inductive loads If you connect an inductive load i e a consumer...

Страница 8: ...gh the load The magnitude of the capacitor is determined using the following equation C k IL k 0 1 2 dependent on the application Only use capacitors of class X2 Units R Ohm U Volt IL Ampere C F If co...

Страница 9: ...inal allocation variants 2 6 1 Private pool possible terminal allocation A1261 I II III IV V VI VII VIII IX X XI Fig 4 Private pool possible terminal allocation I Frequency converter FU II Level switc...

Страница 10: ...hout a sub folder 2 Minimum requirements of the photos JPEG n The aspect ratio e g 16 9 or 3 2 of the photo must cor respond to that of your output equipment e g monitor n The photograph resolution sh...

Страница 11: ...1 pool_2 pool_3 pool_4 pool_5 pool_6 pool_7 pool_8 pool_9 pool_10 JetStream x x x x Massage pump x x x x Neck shower x x x x Cover CLOSE x Under water light x Attraction is ON x ON Attraction is ON OF...

Страница 12: ...the ENTER key in the continuous display of the DUL COMARIN II You are now taken to the central menu item Servomotor not ready 6 00 7 12 LIST CONFIG PARAM CAL HELP SD System free Set Dosing Cl A1257 t...

Страница 13: ...Type NO Low flow contact SAVE CONFIG SERVICE A1258 Type NO Type NO Type NO Type NO Level max Level Alarm Backwash 1 First filtrate 1 Water top up Heating enable JetStream Underwater light Cntrl circu...

Страница 14: ...enu appears 9 In the configuration menu use the vertical arrow keys to select the necessary function and enter the necessary control values Press the ENTER key after each change 10 Finally to confirm...

Страница 15: ...top up Heating enable JetStream Underwater light Cntrl circulation 1 free Circ 1 Fig 12 Configuration menu of the DULCOMARIN II 11 Press the F2 key The service menu appears In this service menu you c...

Страница 16: ...sing an addi tional module The times for the circulation must be set with the F4 CONFIG F2 OPTION TIMER If no times are set then the circula tion will not run automatically To control a 230 V circulat...

Страница 17: ...ppear on the display 3 Set the Filtration speed in normal operation The filtration speed is calculated from the flow rate filter sur face For private applications set a filtration speed of up to 50 m...

Страница 18: ...n rate is reached the controller does not lower the rate any further from this level If you have deactivated redox control so called step lowering is active Here two values must be entered Circulation...

Страница 19: ...l functions to each relay is not universally possible Please observe our allocation suggestion in the appendix of the operating instructions In the appendix you can find a series of the most appropria...

Страница 20: ...to a cleaning process ensuring that any turbidity in the swimming pool is excluded This valve is connected to termi nals P2 P7 and then configured in the operating menu of the Dulcomarin II 5 4 Lower...

Страница 21: ...in operation Measure Always return the system to AUTO mode so that all safety equipment is active Pressing the Start Stop key resets all existing errors The system is once more in AUTO mode In the eve...

Страница 22: ...t a filling time of 0 8 minutes 5 6 2 Two level functions single stage and overflow alarm This function comprises a single stage level function and a forced switching of the circulating pump at Level...

Страница 23: ...the top up water solenoid valve while if the contact is reached an alarm message is output If the contact is activated during a standstill Circulating operation pause of the circulating pump then the...

Страница 24: ...other energy carriers via a heat exchanger if this is required Connection of the F module takes place at the terminals P2 P7 The heating system must be activated in the M module so that it can be set...

Страница 25: ...culation Digital input and MV active The switch makes a contact Circula tion off metering off and switch on delayed The solenoid valve control and the potential free contact must be wired together and...

Страница 26: ...ition Roll cover completely open must be wired to the digital inputs K01 K05 All active actions stop if the cover is being closed or is closed Solely the attraction Underwater light can be manually sw...

Страница 27: ...hed If a massage function is activated then the corresponding symbol appears in the Dulco marin II visualisation and the key naming is the same as the Massage nozzle attraction 5 10 5 Underwater light...

Страница 28: ...ation quantity In this way you receive a precise indication of the flow on the Dulcomarin II display To achieve an overview of the quantity of the fresh water top up there is an option permitting elec...

Страница 29: ...rated in Manual mode Backwashing FW Lev OK FW Time Start Liquid level level measure ment Fresh water top up is also started with a filling time FW Stop Liquid level level measure ment Fresh water top...

Страница 30: ...he action SET Backwasch Emergency STOP Pumping system is faulty If the pumping system reports a fault then no backwashing is carried out until this fault is cleared DELETE Backwash Emergency STOP Pump...

Страница 31: ...Part number Quantity Electrical filter control unit 733849 1 Filter control cover 1041840 1 PT bolt KA35x10 Torx 1001364 5 Terminal diagram label 1042906 1 Nameplate 1025496 1 Folding box 267x216x64...

Страница 32: ...operation no more than insignificant spikes are to be expected Terminal strip XP1 Pin Signal Function 1 L Phase 2 N Neutral conductor 3 PE Protective earth conductor On board fuses n F2 0 63 ampere sl...

Страница 33: ...ting current max 30A for 0 5s Ohmic and inductive up to cos phi 0 4 2 N 3 PE XR4 1 L switched Output relay 230 V feeding R C circuit and varistor fuse F6 Max 1100VA 5A starting current max 30A for 0 5...

Страница 34: ...r interfaces 4 XK2 1 Digital input 5 Max 10 kHz Potential free mechan ical contact or open col lector Isolated to the C and all other interfaces 2 3 4 Description Value Insulation voltage 500 Vpp max...

Страница 35: ...max Output voltage max 18V idle Overvoltage resistant up to 50V no function for output current 0mA at 21 5mA up to 30V otherwise overheating of the control transistor is possible Ripple max 450 ohm a...

Страница 36: ...e digital inputs allocated 5 Question How are the mA outputs allocated 5 Question How are the outputs allocated 6 Question How are the terminals of the F module allocated 5 Question How do I clear an...

Страница 37: ...37...

Страница 38: ...38...

Страница 39: ...39...

Страница 40: ...985358 2 en_GB 2016 ProMinent GmbH Im Schuhmachergewann 5 11 69123 Heidelberg Germany Telephone 49 6221 842 0 Fax 49 6221 842 419 Email info prominent com Internet www prominent com...

Отзывы: