6
Assembly
6.1 Wall mounting
Secure the metering system perpendicular and
upright on a wall or a stable mounting system.
The metering system should be freely accessible.
Select the mounting height you require so that:
n
All components are easily accessible
n
The controller's display can be easily read
n
The controller lid can still be parked in the
[Park position] (150
mm)
n
There is still space for maintenance work beneath the in-line
probe housing (100 mm)
n
There is still room for the chemical storage tank (600 mm)
n
The fluid level of the full chemical storage tanks is below the
metering pumps
n
The maximum priming lift of the metering pumps is not
exceeded.
10 mm
A0924
1
2
3 4
Fig. 10: Hanger bolt
1 Rawlplug (type dependent on substrate and according to stipu‐
lations of the rawlplug manufacturer)
2 Hanger bolt
3 U-washer
4 Hexagonal nut
The system may only be assembled in a separate, well-ventilated
and frost-proof room. Untrained persons must be denied access to
the room by means of structural or organisational measures. It is
recommended to comply with the requirements for plant rooms in
swimming pools specified in DIN 19643.
If the system is delivered as a collection of lose parts or without
metering pumps for installation by the customer, all components or
the external metering pumps must be assembled as specified in
the overview of equipment in chapter
Assembly
20