14.7 Stroke control drive
Voltage
Mains supply fre‐
quency
Capacity
230 V ±10 %
50/60 Hz
6.5 W
115 V ±10 %
60 Hz
6.5 W
14.8 Diaphragm rupture sensor
Install the sensor according to the chapter "Installation, elec‐
trical".
Contact loading, max.
at voltage
Maximum current
30 V DC
1 A.
The diaphragm rupture sensor is an NC.
–
For safety reasons we recommend connecting to a pro‐
tective low voltage, e.g. in accordance with EN 60335-1
(SELV ).
–
The cable can be connected as required.
5–25 V DC, in accordance with Namur or DIN 60947-5-6, potential-free
design.
Data
Value Unit
Nominal voltage *
8 VDC
Power consumption - active surface
uncovered
> 3 mA
Power consumption - active surface cov‐
ered
< 1 mA
Rated switching distance
1.5 mm
* Ri ~ 1 kΩ
Cable colour
Polarity
blue
-
brown
+
a) Contact (Standard for identity code
specification "Displacement body“: A)
a) Namur sensor (for identity code specifi‐
cation "Displacement body“: A)
Technical data