ProFire PF3102-00A Скачать руководство пользователя страница 1

 

 

 

 

                PF3100 Ion Pilot Card Product Manual R 1.0 

PROFIRE 
1.855.776.3473 
[email protected] 

 

Page 1 of 12 

 

 

PROFIRE PF3100 Ion Pilot Card 

PF3102-00 
 

 

 

The PROFIRE PF3100 Ion Pilot card is an igniter and uses ionization to detect flame. 

 
 

Содержание PF3102-00A

Страница 1: ...t Card Product Manual R 1 0 PROFIRE 1 855 776 3473 solutions profireenergy com Page 1 of 12 PROFIRE PF3100 Ion Pilot Card PF3102 00 The PROFIRE PF3100 Ion Pilot card is an igniter and uses ionization...

Страница 2: ...com Page 2 of 12 1 Introduction 3 2 Certifications 3 3 Card Information 4 4 Wiring Diagram 6 5 Mounting Instructions 9 6 Enclosure Specifications 10 7 Instructions for Use 10 8 Preventative Maintenanc...

Страница 3: ...controller card or a Network card Model Types Model Number Name Description PF3102 00A Ion Pilot Card Zone 1 Aluminum enclosure 2 Certifications PROFIRE strives to ensure that certifications are upda...

Страница 4: ...Card Product Manual PROFIRE 1 855 776 3473 solutions profireenergy com Page 4 of 12 3 Card Information Card Specifications The ambient temperature rating for the Ion Pilot Card is 40 C 40 F to 60 C 14...

Страница 5: ...e primary winding of the ignition coil white wire Coil Drive Output Yes 14 VDC 360mA Terminal Descriptions Main Ion Pilot Ion Connect each of these inputs to a Kanthal flame rod placed directly in the...

Страница 6: ...must be connected between the positive and negative terminals The negative terminal is NOT directly connected to ground This output is driven by 12V and will only work with 12V solenoid valves EGND Th...

Страница 7: ...FIRE 1 855 776 3473 solutions profireenergy com Page 7 of 12 Single Rod Pilot Wiring The single rod pilot configuration is used for a single rod for flame detection and pilot detection Older Model wit...

Страница 8: ...FIRE 1 855 776 3473 solutions profireenergy com Page 8 of 12 Dual Rod Pilot Wiring Dual rod configuration is used when two separate rods for pilot ignition and flame detection are used Older Model wit...

Страница 9: ...me Detect Dual Rod Pilot only 7mm 0 25 inches ignition wire Wire should be limited to 3 meters 10 ft 7 Board to Burner 14 AWG Wire should be limited to 3 meters 10 ft 10 Coil to Pilot Ignition Rod 7mm...

Страница 10: ...rd works correctly and efficiently the following maintenance and inspection procedures should be followed Ensure that all wires are connected correctly Minimize copper wire exposure Check for corrosio...

Страница 11: ...y PROFIRE is not recommended Failure to observe the following warnings may result in death electrocution property damage product damage product damage government fines or malfunction of the product it...

Страница 12: ...l as the Ion and the secondary of the ignition coil all pose this risk 10 PROFIRE Contact Information If you have any concerns or questions about this product please contact PROFIRE as follows U S 1 8...

Отзывы: