background image

 

USER GUIDE

HLS 44-SER

V1.1.0 (22.04.2014) 

1 (6) 

 

Produal Oy 

Keltakalliontie 18, 48770 Kotka FINLAND 

Tel: +358 10 219 9100 / Fax: +358 5 230 9210 

[email protected] 

www.produal.com 

Information is subject to change without prior notice. 

Commissioning tool HLS 44-SER 

HLS 44-SER is a tool for commissioning HLS 44 and HLS 44-V controllers. By using this tool the commissioning is fast and you may rely on 
that the settings are as planned.  

It is useful to plan and program the settings to the tool with care in advance. After that, you can load the settings to the controllers in office or 
on the installation site during commissioning. 

This user guide is for the commissioning tool software version 1.1.0 or newer. The tool software version shows on the tool display when the 
power is switched on. 

PROFILES 

HLS 44-SER commissioning tool contains fixed factory settings (PRSET 1) for HLS 44 and HLS 44-V, memory slots for 5 user defined 
solutions (SET 1...5) and 4 pre-programmed application profiles (SET 6...9). All parameters of SET 1...9 can be changed for a best possible 
room control solution. For more information see the instructions of HLS44 and HLS 44-V. 

Pre-programmed applications (SET 6…9) are the following: 

SET 6 

Heating by radiator and cooling by beam 

SET 7 

Heating and cooling by a fan coil unit 

SET 8 

Heating by radiator and cooling by VAV and beam (VAV control based on CO

2

 concentration) 

SET 9 

Heating by radiator and cooling by beam (dampers and lights ON/OFF by PIR detection; HLS 44-V) 

GETTING STARTED 

1. 

Remove the controller cover. 

2. 

Connect the commissioning tool cable to the controller programming terminal. 

 

A. Commissioning tool cable 

NOTE:

 Connecting the tool to the programming terminal will disconnect the controller from the Modbus communication. 

3. 

Connect the supply voltage either to the commissioning tool or the controller. 

IMPORTANT:

 Do not connect the supply voltage to both devices. 

4. 

Check that the software version numbers are compatible. 

The software versions are shown on the displays when you switch on the power. See the compatible software versions from the 
following table. 

HLS 44-SER 
software version 

Compatible HLS 44 and 
HLS 44-V software versions 

1.0.0 

1.0.0 -> 1.0.2 

1.1.0 

1.1.0 -> 1.1.2 

1.1.3 

1.1.3 

1.1.4 

1.1.4 -> 1.1.7 

1.1.8 

1.1.4 -> 1.1.9 

Содержание HLS 44-SER

Страница 1: ...hanged for a best possible room control solution For more information see the instructions of HLS44 and HLS 44 V Pre programmed applications SET 6 9 are the following SET 6 Heating by radiator and cooling by beam SET 7 Heating and cooling by a fan coil unit SET 8 Heating by radiator and cooling by VAV and beam VAV control based on CO2 concentration SET 9 Heating by radiator and cooling by beam dam...

Страница 2: ... which you want to store the parameters NOTE The selected profile will be overwritten with the new parameters You cannot recover the overwritten profiles 2 Press the button 3 Make the wanted adjustments in the menu See the detailed parameter setting instructions from the HLS 44 or HLS 44 V user guide 4 Load the parameters to the controller LOADING PARAMETERS FROM THE CONTROLLER TO THE COMMISSIONIN...

Страница 3: ...drive Cooling 0 10V by modbus Y3 0 1000 0 10 00 V 0 No modbus overdrives chosen The value has no affect see coils 1 10 40005 Overdrive Heating PWM by modbus A2 0 1000 0 00 100 0 0 No modbus overdrives chosen The value has no affect see coils 1 10 40006 Overdrive Heating 0 10V by modbus Y4 0 1000 0 10 00 V 0 No modbus overdrives chosen The value has no affect see coils 1 10 40007 Overdrive VAV by m...

Страница 4: ...Cooling 0 10V by modbus Y3 0 1000 0 10 00 V 0 No modbus overdrives chosen The value has no affect see coils 1 10 40005 Overdrive Heating PWM by modbus A2 0 1000 0 00 100 0 0 No modbus overdrives chosen The value has no affect see coils 1 10 40006 Overdrive Heating 0 10V by modbus Y4 0 1000 0 10 00 V 0 No modbus overdrives chosen The value has no affect see coils 1 10 40007 Overdrive VAV by modbus ...

Страница 5: ...04 Overdrive Cooling 0 10V by modbus Y3 0 1000 0 10 00 V 0 No modbus overdrives chosen The value has no affect see coils 1 10 40005 Overdrive Heating PWM by modbus A2 0 1000 0 00 100 0 0 No modbus overdrives chosen The value has no affect see coils 1 10 40006 Overdrive Heating 0 10V by modbus Y4 0 1000 0 10 00 V 0 No modbus overdrives chosen The value has no affect see coils 1 10 40007 Overdrive V...

Страница 6: ...ive Cooling 0 10V by modbus Y3 0 1000 0 10 00 V 0 No modbus overdrives chosen The value has no affect see coils 1 10 40005 Overdrive Heating PWM by modbus A2 0 1000 0 00 100 0 0 No modbus overdrives chosen The value has no affect see coils 1 10 40006 Overdrive Heating 0 10V by modbus Y4 0 1000 0 10 00 V 0 No modbus overdrives chosen The value has no affect see coils 1 10 40007 Overdrive VAV by mod...

Отзывы: