12.5.5
Voltage at the end of the segment
The resistance of the cable causes a lower voltage at the end of the cable. At least 9V should be available for
the last device at the end of the cable. The following calculation is a ‘worst case’ scenario where all devices are
connected at the end of the cable:
Fig. 89 - Example of voltage calculation at the end of the cable
In this example the voltage at the end of the cable is 24 V - (0.05A * 44 * 1.5) =
20.7 V
Trunk line = 1450 m
U
S
= 24 V
U
B
> U
MIN
L
SEG
= 1500 m
I
SEG
= 50 mA
10 m
20 m
20 m
U
B
= U
S
–
(I
SEG
* R
CABLE
* L
SEG
)
(where U
B
> U
min
)
U
B
= Bus voltage at the last device (V)
U
S
= Voltage of the segment coupler (V)
I
SEG
= Total current In a segment (A)
R
CABLE
= Resistance per unit length of the cable (
Ω
/km)
L
SEG
= Length of all cables in the segment, including stubs (km)
U
min
= Minimal specified operating voltage of the last device (V)
I
B1
= 10 mA
I
B2
= 12 mA
I
B3
= 18 mA
I
S
= 500 mA
I
SEG
< I
S
I
FDE
= 10 mA
I
SEG
= 60mA
I
B0
= 10 mA
Fig. 88 - Example of current consumption calculation in a PA segment
Содержание ComBricks
Страница 1: ...User Manual ...
Страница 132: ...ComBricks User Manual v6 4 0 January 18 PROCENTEC 132 219 ...
Страница 213: ...ComBricks User Manual v6 4 0 January 18 PROCENTEC 213 219 44 Certificates ...
Страница 214: ...ComBricks User Manual v6 4 0 January 18 PROCENTEC 214 219 ...
Страница 215: ...ComBricks User Manual v6 4 0 January 18 PROCENTEC 215 219 ...
Страница 216: ...ComBricks User Manual v6 4 0 January 18 PROCENTEC 216 219 ...
Страница 217: ...ComBricks User Manual v6 4 0 January 18 PROCENTEC 217 219 45 Notes ...
Страница 218: ...ComBricks User Manual v6 4 0 January 18 PROCENTEC 218 219 ...