Industrial Personal Computer Connections
60
Grounding
Overview
The grounding resistance between the Industrial Personal Computer ground and the
ground must be 100
or less. When using a long grounding wire, check the
resistance and, if required, replace a thin wire with a thicker wire and place it in a
duct. In addition, refer to the table below for maximum lengths of various wire
thicknesses.
Ground Wire Dimensions
Precaution
Dedicated Ground
Connect the Industrial Personal Computer ground to a dedicated ground:
Wire Cross-section
Maximum Line Length
2.5 mm
2
(AWG 13)
30 m (98 ft)
60 m (196 ft) round trip.
WARNING
UNINTENDED EQUIPMENT OPERATION
Use only the authorized grounding configurations shown below.
Confirm that the grounding resistance is 100
or less.
Test the quality of your ground connection before applying power to the device.
Excess noise on the ground line can disrupt operations of the Industrial
Personal Computer.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Industrial Personal
Computer
Содержание PS-4600 Series
Страница 1: ......
Страница 12: ...About the Book 12...
Страница 14: ...General Overview 14...
Страница 26: ...Important Information 26...
Страница 56: ...Implementation 56...
Страница 72: ...Industrial Personal Computer Connections 72...
Страница 78: ...Configuration of the BIOS 78 Platform Information The figure shows the Main submenu...
Страница 118: ...Hardware Modifications 118 The figure shows the dimensions of the UPS battery unit...
Страница 170: ...Hardware Modifications 170...
Страница 172: ...Installation 172...
Страница 192: ...192...
Страница 196: ...After sales service 196...