PL-6930 / PL-7930 Series User Manual
7-8
7.2
Monitoring the PL Status
7.2.1
Setup Procedures
Double-click [System Monitor Property] in [Control Panel] to display the System Monitor Property screen.
Set the actions when the allowable range for the preset monitoring features is exceeded (when an error occurs).
The following table lists the description of each action.
•
You can also display the System Monitor Property screen by selecting [Start] -> [Program] ->
[System Monitor].
Item
Operation
Buzzer
Sounds a beep as an alarm. (Cannot be set up when a checkmark is put in
the “OS Shutdown” checkbox.
Pop-up Message
Displays error messages as pop-up messages. (The monitoring item and
description of the error are displayed.)
OS Shutdown
Shuts down the operating system. (The shutdown confirmation message is
not displayed.)
OS Restart
Resets the hardware.
Enable
Select or deselect this option to enable or disable each setting of the
monitoring feature.
LED
The front LED lights orange/red.
DOUT0 to 3
Output from the RAS port.
Enable or disable the
feature.
Specify the operation to
be performed when the
condition exceeds the
allowable range.
Enter the message to
be displayed as a
pop-up message.
Set the timer