Prella PLH-24V Скачать руководство пользователя страница 1

TESTING

1. All the alarm signal services, releasing device and

extinguisher system should be disengaged during the

test period and must be re-engaged immediately at the

conclusion of testing.

2. After energizing the detector head for approximately

one minute, check to see the indicator red LED

flashing once every 30 seconds. If red LED fails to

flash, it indicates the non-functioning of the detector or

faulty wiring. Re-check the wiring or replace the

detector if necessary.

PLH-24V 
Installation Wiring Diagram

Conventional Heat Detector 

 

TYPICAL WIRING DIAGRAM 

Figure 1(a)

 shows the typical wiring diagram of the 

multiple-station smoke detector system.

 

Figure  1(b)

  shows  the  typical  wiring  diagram  of  the 

4-wire multiple-station smoke detector system. 

WARNING

TO PREVENT DETECTOR CONTAMINATION AND

SUBSEQUENT

WARRANTY

CANCELLATION,

THE

SMOKE DETECTOR MUST REMAIN COVERED UNTIL

THE AREA IS CLEAN AND DUST FREE. 

INSTALLING THE BASE

1. To insure proper installation of the detector head to the

base, all the wires should be properly addressed at

installation:

(A) Position all the wires flat against terminals.

(B) Fasten the wires away from connector terminals.

2. If you use a jumper wire to connect the poles of

terminal 2 and 3, 4 when testing the detector loop

continuity, be sure to remove the jumper wire prior to

the installation of the detector head.

 

DO NOT PLACE LINKS BETWEEN THE WIRING POSITIONS 

OF TERMINALS 2 AND 4, 5 TO PROVIDE POWER 

SUPERVISION 

Note: relay and the remote indicator could not 

be used at the same time

INSTALLING THE HEAD

1. Align the components as shown in Figure 2.

2. Mate the detector head onto the base and twist

clockwise to secure it.

3. Do not install the detector head until the area is

thoroughly cleaned of construction debris, dusts, etc.

LONG ALIGNMENT MARK

SHORT ALIGNMENT MARK

BASE

LED

DETECTOR HEAD

Fig. 2 Mating detector head onto base

The following requirements are for which with 

relay output:

1A@30VDC,  

0.5A@125VAC

Rated load of relay:

5. The base of the smoke detector can be mounted

directly onto an electrical junction box such as an

octagonal (75mm, 90mm or 100mm), a round (75mm),

or a square (100mm) box without using any type of

mechanical adapter.

4. Open area smoke detectors are intended for mounting

on a ceiling or a wall in accordance with the fire

standard in your country.

3. The end-of-line device shown in fig. 1(a) and 1(b)

should be compatible with the control unit. The

end-of-line supervisory relay used should be rated for

the DC power voltage used.

The wiring diagram of 2/3 wired LED remote indication

Do not place links between terminals 1,2 and 4,5 to provide wire 

continuity monitoring

Note: relay output of the device is fully isolated (Dry)

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

REMOTE LED

INDICATOR

EOL

RESISTOR

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

4 Wired Normally Open Wiring Diagram

EOL

RESISTOR

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

4 Wired Normally Close Wiring Diagram

EOL

RESISTOR