Sabre P 

 Model PD603 

Process Meter 

Instruction Manual 

 

• 

0-20, 4-20 mA, 0-5, 1-5, 0-10, 

±

10 V Inputs 

• 

Type 4X, NEMA 4X, IP65 Front 

• 

Shallow Depth Case 3.6" Behind Panel 

• 

4 Digit Display, 0.56" (14 mm) High, Red LEDs 

• 

Easy Front Panel Programming 

• 

Scale without a Signal Source 

• 

Calibrate with a Signal Source 

• 

Maximum/Minimum Display 

• 

Universal Power Supply 85-265 VAC 

• 

12-36 VDC/12-24 VAC Power Option 

• 

24 VDC @ 200 mA Transmitter Supply Option 

PRECISION DIGITAL CORPORATION 

19 Strathmore Road  •  Natick MA 01760 USA 
Tel (800) 343-1001 • Fax (508) 655-8990

 

www.predig.com 

Содержание PD603

Страница 1: ...ay 0 56 14 mm High Red LEDs Easy Front Panel Programming Scale without a Signal Source Calibrate with a Signal Source Maximum Minimum Display Universal Power Supply 85 265 VAC 12 36 VDC 12 24 VAC Powe...

Страница 2: ...document is subject to change without notice Precision Digital makes no representations or war ranties with respect to the contents hereof and specifically disclaims any implied warranties of merchan...

Страница 3: ...A2502 2 Plastic NEMA 4X Enclosure Through Door PDA2503 3 Plastic NEMA 4X Enclosure Through Door PDA2504 4 Plastic NEMA 4X Enclosure Through Door PDA2505 5 Plastic NEMA 4X Enclosure Through Door PDA250...

Страница 4: ...beling 11 Power Connections 11 Signal Connections 12 SETUP AND PROGRAMMING 14 Front Panel Buttons and Status LED Indicators 15 Display Functions and Messages 16 Main Menu 17 Setting Numeric Values 18...

Страница 5: ...f Figures Figure 1 Panel Cutout and Mounting 10 Figure 2 Connector Labeling Meter with 24 V Supply 11 Figure 3 Power Connections 11 Figure 4 Transmitter Powered by Ext Supply or Self Powered 12 Figure...

Страница 6: ...f programmed settings NON VOLATILE MEMORY All programmed settings are stored in non volatile memory for a minimum of ten years if power is lost POWER OPTIONS 85 265 VAC 50 60 Hz 90 265 VDC 20 W max or...

Страница 7: ...st for details Process Input INPUTS Field selectable 0 20 4 20 mA 0 5 1 5 0 10 V or 10 V ACCURACY 0 05 FS 1 count FUNCTION Linear TEMPERATURE DRIFT 50 PPM C from 0 to 65 C ambient DECIMAL POINT Up to...

Страница 8: ...SIONS EN 55011 1998 Group 1 Class A ISM emissions requirements Radiated Emissions Class A AC Mains Conducted Emissions Class A IMMUNITY EN 61000 6 2 2001 EMC heavy industrial generic immunity standard...

Страница 9: ...t of entry representing installations designed to optimize EMC performance Declaration of Conformity available at www predig com SAFETY INFORMATION CAUTION Read complete instructions prior to instal l...

Страница 10: ...commended minimum panel thickness to maintain Type 4X rating 0 06 1 5 mm steel panel 0 16 4 1 mm plastic panel Remove the two mounting brackets provided with the meter back off the two screws so that...

Страница 11: ...ensure personnel safety Connector Labeling The connectors label affixed to the meter shows the location of the connectors available with requested configuration 24V OUT DW1911 POWER X X V mA COM Facto...

Страница 12: ...20 mA Transmitter SIGNAL CONNECTOR COM SIGNAL CONNECTOR mA 2 1 3 5 4 V X X 2 Wire 4 20 mA Self Powered Transmitter Figure 4 Transmitter Powered by Ext Supply or Self Powered COM SIGNAL CONNECTOR mA 2...

Страница 13: ...l SIGNAL CONNECTOR 2 1 3 5 4 Voltage Signal COM mA V X X COM SIGNAL CONNECTOR mA 2 1 3 5 4 V X X 3 Wire Voltage Transducer Signal 2 1 24V OUT P P Figure 6 Voltage Input Connections The meter is capabl...

Страница 14: ...d volts The calibration equipment is certified to NIST standards Overview There are no jumpers involved in the setup process of the meter The switch located between the SIGNAL and the RJ11 connectors...

Страница 15: ...t Up arrow Max Enter Ack Press the Menu button to enter or exit the Programming Mode at any time Press the Right arrow button to move to the next digit during digit programming Press the Up arrow butt...

Страница 16: ...or 10 VDC input dec p Decimal point Set decimal point for process inputs prog Program Enter the Program menu scal Scale Enter the Scale menu Cal Calibrate Enter the Calibrate menu inp1 Input 1 Calibra...

Страница 17: ...ming Mode then press Up arrow button to scroll main menu 9603 setu prog pass Run Mode Press Menu at any time to exit and return to Run Mode Changes made to settings prior to pressing Enter Ack are not...

Страница 18: ...t and Up arrow to increment digit value The digit being changed is displayed brighter than the rest Press the Enter Ack button at any time to accept a setting or Menu button to exit without saving cha...

Страница 19: ...etu inpt dec p Setting the Input Signal inpt Enter the Input menu to set up the meter to display current 4 20 or voltage 0 10 inputs The voltage input is capable of accepting any signal from 10 to 10...

Страница 20: ...p Decimal point may be set with up to three decimal places or with no decimal point at all Pressing the Up arrow moves the decimal point one place to the right until no decimal point is displayed then...

Страница 21: ...he factory The meter is factory calibrated prior to shipment for all input types in milliamps and volts The calibration equipment is certified to NIST standards Use the Scale menu to scale process inp...

Страница 22: ...e is not needed to scale the meter simply program the inputs and corresponding display values dis1 00 0 Press Enter to Accept Setting inp2 Scale Input 2 inp1 Set Input 1 Value scal 04 00 Set Display 1...

Страница 23: ...caused by any of the following conditions 1 Input signal is not connected to the proper terminals or it is con nected backwards 2 Wrong signal selection in Setup menu 3 Minimum input span requirement...

Страница 24: ...e calibrated to display the process in engineering units by applying the appropriate input signal and following the calibration procedure The use of a calibrated signal source is strongly recommended...

Страница 25: ...git password For instructions on how to program numeric values see Setting Numeric Values page 18 pass unlC 0000 Program Password loCd Run Mode Record the password for future reference If appropriate...

Страница 26: ...red is incorrect the meter displays LoCd Locked for about two seconds then it returns to Run Mode To try again press Enter Ack while the Locked message is displayed Forgot the Password The password ma...

Страница 27: ...eering units from 1999 to 9999 e g a signal from 10 to 10 VDC could be displayed as 5000 to 5000 Front Panel Buttons Operation Button Symbol Description Press to enter or exit Programming Mode view se...

Страница 28: ...Min 1 Press Up arrow Max button to display maximum reading since the last reset power up 2 Press Up arrow Max again to display the minimum reading since the last reset power up 3 Press Enter Ack to ho...

Страница 29: ...l PD603 Process Meter Instruction Manual MOUNTING DIMENSIONS 1 76 45mm 0 59 15mm 3 2 81mm 2 45 62mm 3 6 91mm Figure 7 Meter Dimensions Side View 3 61 92mm 2 50 64mm 4 68 119mm Figure 8 Case Dimensions...

Страница 30: ...locked enter correct four digit password to unlock Meter displays error message during calibration err Check 1 Signal connections 2 Input selected in Setup menu 3 Minimum input span requirements Meter...

Страница 31: ...Meter Instruction Manual QUICK USER INTERFACE REFERENCE GUIDE Run Mode Setup Program Password Display Max Min Input 4 20 mA 0 10 V Locked Unlocked Scale Calibrate To Password Decimal Point dddd d ddd...

Страница 32: ...ease Call 800 610 5239 or 508 655 7300 Fax 508 655 8990 Email support predig com For Sales Support or to place an order please Call 800 343 1001 or 508 655 7300 Fax 508 655 8990 Email sales predig com...

Отзывы: