Helios Large Display Analog Input Batch Controller Instruction Manual
PD2-6210
18
RS485 Output Connections
An RS-485 connector is provided for the use of advanced Modbus
®
serial communications. This connector converts the serial output of
the meter to balanced, full or half-duplex RS-485 signals. It has a
removable screw terminal connector for the RS-485 terminals which
includes Transmit Data (DO) and (/DO), Receive Data (DI) and (/DI),
and Signal Ground. Baud rates are adjustable and handled by the
meter (see Modbus RTU Serial Communications on page 52 for
more information).
The RS-485 connector has three diagnostic LEDs: a Power (PWR)
LED to show when the adapter is powered properly, a Transmit Data (TX) LED to show when the adapter
is sending data out from the PC side, and a Receive Data (RX) LED to show when the adapter is
receiving data from the meter.
Installation
Figure 15 shows the connection of a meter to a PC using the RS485 output connector and a PDA7485
RS-232 to RS-422/485 converter in an RS-422 network. Figure 16 shows the connection of several
meters to a PC using a PDA7485 RS-232 to RS-422/485 converter in an RS-485 network.
When using more than one meter in a multi-drop mode, each meter must be provided with its own unique
address. The meter address (Slave ID) may be programmed between 1 and 247. The transmit delay may
be set between 0 and 199 ms. The parity can be set to even, odd, or none with 1 or 2 stop bits.
To change the meter address:
1. Press and hold the
Menu
button for three seconds to access
Advanced Features
menu of the meter.
2. Press
Up
arrow until Serial (
SEriaL
) menu is displayed and press
Enter
,
Addres
is displayed.
3. Press
Enter
to change meter address using
Right
and
Up
arrow buttons. Press
Enter
to accept.
4. Press
Menu
button to exit and return to Run Mode.
Figure 15. RS-422 or RS-485 Wiring
Notes:
1. Termination resistors are optional and values depend on the cable length and characteristic
impedance. Consult the cable manufacturer for recommendations.
2. Refer to RS-232 to RS-422/485 Converter documentation for further details.
3. Use shielded cable, twisted-pairs plus ground. Connect ground shield only at one location.