P
RO
V
U
™ PD6363 Dual Analog Input Rate/Totalizer
Instruction Manual
42
Advanced Features Menu
To simplify the setup process, functions not needed
for most applications are located in the
Advanced
Features
menu.
Press and hold the Menu button for three seconds to
access the advanced features of the meter.
Advanced Features Menu &
Display Messages
The following table shows the functions and
messages of the
Advanced Features
menu in the
order they appear in the menu.
Advanced Features Menu & Display Messages
Display
Parameter
Action/Setting
Gate
Gate
Enter Gate function
menu
Lo G
Low gate
Program Low gate
value
Hi G
High gate
Program High gate
value
filter
Filter
Enter the Filter menu
Ch-A
Channel A
Set filter speed for
channel A
Ch-b
Channel B
Set filter speed for
channel B
Lo Spd
Low speed
Set the contact
de-bounce filter value
Hi Spd
High speed
Select high speed filter
Round
Round
Set the rounding value
for the display
seriAl
Serial
Set serial
communication
parameters
SlaVId
Slave ID
Set slave ID or meter
address
Baud
Baud rate
Select baud rate
Tr dLY
Transmit delay
Set serial
communication transmit
delay
Parity
Parity
Select parity
Even, Odd, or None
with 1 or 2 stop bits
t-byt
Time byte
Set byte-to-byte timeout
SelEct
Select
Enter the Select menu
(function, math,
constant, cutoff, count,
Aout programming)
Functn
Input signal
conditioning
Select linear function
parameters
Ch-A
Channel A
Select menu for
channel A
Ch-b
Channel B
Select menu for
channel B
Linear
Linear
Set meter for linear
function and select
number of linearization
points
No pts
Number of
points
Set the number of
linearization points
(default: 2)
Advanced Features Menu & Display Messages
Display
Parameter
Action/Setting
nmath
Math
Select the channel C
math function
Sunm
Sum
C = (A+B+P)*F
Dif
Difference
C = (A-B+P)*F
difabs
Abs difference
C = ((Absolute value of
(A-B))+P)*F
Avg
Average
C = (((A+B)/2)+P)*F
nmulti
Multiplication
C = ((A*B)+P)*F
DiVide
Divide
C = ((A/B)+P)*F
Hi-ab
Max of A or B
C = ((High value of
channel A or B)+P)*F
Lo-ab
Min of A or B
C = ((Low value of
channel A or B)+P)*F
Drauw
Draw
C = ((A/B)-1)*F
uw Avg
Weighted avg.
C = ((B-A)*F)+A
ratio
Ratio
C = (A/B)*F
Ratio2
Ratio 2
C = ((B-A)/A)+P)*F
Concen
Concentration
C = (A/(A+B))*F
Sunm t
Sum total
C = (tA+tB+P)*F
Sunmgt
Sum grand
total
C = (GtA+GtB+P)*F
Dif t
Diff. of total
C = (tA-tB+P)*F
Dif gt
Difference of
grand total
C = (GtA-GtB+P)*F
Tratio
Total ratio
C = (tA/tB)*F
t-rat2
Total ratio 2
C = ((tB-tA)/tA)*F
T pct
Total percent
C = (tA/(tA+tB))*100
Const
Constant
Enter math equation
constants
adder
Adder
Addition constant used
in channel C math
calculations (P)
factor
Factor
Multiplication constant
used in channel C math
calculations (F)
CutofF
Cutoff
Set low-flow cutoff
Ch-A
Channel A
Set low-flow cutoff for
Channel A
Ch-b
Channel B
Set low-flow cutoff for
Channel B
Count
Count
Set total count direction
Ch-A
Channel A
Set total count direction
for Channel A
Ch-b
Channel B
Set total count direction
for Channel B
Tot C
Total count
Set direction of total
count
Gtot C
G. total count
Set direction of grand
total count
up
Count up
Count up
Douwn
Count down
Count down
C strt
Count start
Enter count down start
value
AoutPr
Analog output
programming
Program analog output
parameters
Aout 1
*
Analog output 1
Program analog output
1 (*1-3) parameters
Source
Source
Select source for the
4-20 mA output