PDW30 Point-to-Point Wireless Bridge Instruction Manual
6
RS485 Modbus
®
RTU Serial Comms
Compatibility
EIA-485
Connectors
Removable screw terminal con-
nector
Max Distance
3,937' (1,200 m) max
Baud Rate
1200
– 57,600 bps
Transmit Time
Delay
Programmable between 0 and 199
ms
Data
8 bit (1 start bit, 1 or 2 stop bits)
Parity
Even, Odd, or None with 1 or 2 stop
bits
Byte-To-Byte
Timeout
0.01
– 2.54 second
Turn Around
Delay
Less than 2 ms (fixed)
PDW Manager Software
System Re-
quirements
Microsoft
®
Windows
®
XP/Vista/7/8/10
Communica-
tions
USB 2.0 (Standard USB A to Micro
USB B)
Configuration
Configure devices one at a time
Safety Information
Caution
:
Read complete instructions
prior to installation and operation of the
meter.
Warning
:
Read all product labels
completely and follow all instructions
and requirements listed on the labels
for installation or service.
Warning!
Installation and service should be performed only by trained ser-
vice personnel. Service requiring replacement of internal compo-
nents must be performed at the factory.
Installation
All pushbuttons and wiring connectors are accessed by opening the enclosure. To access electri-
cal connectors, remove the 2 captive screws and remove the meter assembly. Pushbuttons may
also be accessed using the magnet assembly if reed switches are installed.
Unpacking
Remove both units from box. Inspect the packaging and contents for damage. Report damages, if
any, to the carrier. If any part is missing or the units malfunction, please contact your supplier or
the factory for assistance.
!