Loop Leader PD6620 Series Loop-Powered Flow Rate/Totalizers
Instruction Manual
19
Main Menu
The main menu consists of all the meter’s program-
mable functions:
Input
,
Output, Advanced,
and
Dis-
play
.
•
Press
Menu
button to enter
Programming Mode
then press the
Right-Arrow
button to move for-
ward through the menu and the
Up-Arrow
button
to move back.
•
Press
Menu
at any time to go back one level or
press & hold to exit and return to
Run Mode
.
Changes made to settings prior to pressing
Enter
are not saved.
•
Changes to the settings are saved to memory
only after pressing
Enter/F3
to confirm the set-
ting or pressing
Enter/F3
at the
SAVE?
screen
when available.
Note:
The
BARGRAPH
menu appears in the PD6624/8
menu only.
Setting Numeric Values
The numeric values are set using the
Right
and
Up-Arrow
buttons.
1. Press
Right
-
Arrow
to select next digit and
Up
-
Arrow
to increment digit value. The
selected digit will flash.
2. Press and hold
Up
-
Arrow
to auto-increment
the display value. If you have made a
mistake or would like to enter a new value,
select the left-most digit and press and hold
the
Right
-
Arrow
button until all digits reset
to zero.
3. Press the
Enter
button at any time to accept
a setting or
Menu
button to exit without
saving changes.
Note:
the underscore in the graphic below is provided
to show which digit would be flashing.
Scaling the 4-20 mA Input (
INPUT
)
It is
very important
to read the following information
before proceeding to program the meter:
•
The meter is factory calibrated prior to shipment
to display 0.00 to 100.00 gal/s, which corre-
sponds to the 4-20 mA input. The calibration
equipment is traceable to NIST standards.
•
A calibrated signal source is not needed to scale
the meter.
Enter the
Input
menu to scale the meter to display the
4-20 mA input. The input can accept any signal from
4 to 20 mA.
DSP 1
+00,000.00
DSP 1
00,000.00
Select
Digit to
Change
DSP 1
00,050.00
Increment
Selected
Digit
SCALE
INPUT 2
Accept
Setting
SETUP
INPUT
SCALE
UNITS
SCALE
INPUT 1
SCALE
DISP 1
TIME
/SECOND
UNIT
GAL/S
/SECOND
/MINUTE
/HOUR
/DAY
Rate Time
Bases
INP 1
04.000
INP 1
mA
Flashes Units
Momentarily
DSP 1
+00,000.00
SCALE
INPUT 2
INP 2
20.000
SCALE
DISP 2
DSP 2
+00,100.00
SAVE?
SETUP
INPUT
GAL/
(T)
L/
(T)
IGAL/
(T)
Rate Units
M3/
(T)
BBL/
(T)
BUSH/
(T)
cuYD/
(T)
cuFt/
(T)
cuIn/
(T)
LiBBL/
(T)
BBBL/
(T)
HECtL/
(T)
AF/
(T)
CUSTM/
(T)
52.86
38,418.2
SETUP
INPUT
SETUP
OUTPUT
SETUP
ADVANCED
SETUP
DISPLAY
OPEN
COLLECTR
ADV
RATE
DSPLY
UNITS
OUT
RELAY
OUT
4-20 mA
OUT
CONTROL
CUTOFF
FILTER
PASSWRD
USER
SYSTEM
DSPLY
DEC.PT
DSPLY
COMMA
DSPLY
TOP
DSPLY
DOTTOM
SCALE
UNITS
SCALE
INPUT 1
SCALE
DISP 1
SCALE
INPUT 2
SCALE
DISP 2
SAVE?
ADV
TOTAL
ADV
GTOTAL
Run Mode
DSPLY
BARGRAPH
*PD6624/8
Only
*