Operation Manual
This brief manual is primarily meant for quick reference to wiring
connections and parameter searching. For more details on
operation and application; please log on to www.ppiindia.net
FLOREX
Flow Rate Indicator Cum Totaliser
Parameters
Settings
VIEW ONLY PARAMETERS
Total Time
Minimum Flow Rate
Maximum Flow Rate
No. Of Overflows
Time (HH:MM:SS)
00:00:00
MIN. FLOW RATE
0
MAX. FLOW RATE
100
NO.OF OVER FLOW
0
Serial Write
Permission
Parity
None
Even
Odd
(Default : Even)
Serial ID
1 to 127
(Default : 1)
Baud Rate
4800
9600
19200
38400
57600
(Default : 9600 bps)
Parameters
Settings
(Default Value)
SERIAL CONFIGURATION PARAMETERS
Disable
Enable
(Default : Disable)
User Linearisation
Activation
1 to 32
(Default : 2)
Total Points
1 to Max. Selected
(Default : 1)
Points Number
-19999 to 30000
(Default : 0)
Actual Point
Derived Point
Parameters
Settings
(Default Value)
USER LINEARISATION PARAMETERS
Settings
(Default Value)
SUPERVISORY PARAMETERS
Flow Alarm SP
Adjustment on
Operator PAGE
Total Alarm SP
Adjustment on
Operator PAGE
Storage of Min./ Max.
Flow Rate Activation
Parameters
Parameters
Settings
(Default Value)
OPERATOR PARAMETERS
Alarm Acknowledge
Min./Max. Reset
Command
Passcode Value
Total Reset
Command
0 to 250
(Default : 0)
Passcode Value
Flow Alarm-1
Setpoint
Flow Alarm-2
Setpoint
Total Alarm-1
Setpoint
0 to 99999999
(Default : 5000000)
Total Alarm-1 Ext.
Setpoint
Total Alarm-2
Setpoint
0 to 125
(Default : 0)
Total Alarm-2 Ext.
Setpoint
Alarm-1 Type
None
Process Low
Process High
(Default : None)
Alarm-1 Setpoint
0 to 30000
(Default :
For Process Low : 0,
For Process High : 1000)
1 to 30000
(Default : 2)
Alarm-1 Hysteresis
Alarm-1 Inhibit
(Default : No)
No
Yes
(Default : Normal)
Normal
Reverse
Alarm-1 Logic
Alarm-1 Latch
(Default : Disable)
Disable
Enable
Parameters
Settings
(Default Value)
FLOW ALARM PARAMETERS
Alarm-2 Type
Alarm-2 Setpoint
0 to 30000
(Default :
For Process Low : 0,
For Process High : 1000)
Parameters
Settings
(Default Value)
1 to 30000
(Default : 2)
Alarm-2 Hysteresis
Alarm-2 Inhibit
(Default : No)
No
Yes
(Default : Normal)
Normal
Reverse
Alarm-2 Logic
Alarm-2 Latch
(Default : Disable)
Disable
Enable
Parameters
Settings
(Default Value)
TOTAL ALARM PARAMETERS
Alarm-1 Set Point
Alarm-1 Extension
Set Point
Alarm-1 Logic
Alarm-1 Time
0 to 99999999
(Default : 5000000)
0 to 125
(Default : 0)
Alarm-1 Activation
Retransmission
Output Type
Low Range
High Range
-19999 to 30000
(Default : 0)
-19999 to 30000
(Default : 1000)
Parameters
Settings
(Default Value)
RETRANSMISSION PARAMETERS
0 to 20 mA
4 to 20 mA
0 to 5 Volts
0 to 10 Volts
(Default : 0 to 20 mA)
Input Type
Time base
Resolution
Refer Table -1
(Default : 0 to 20mA)
Second
Minute
Hour
(Default : Seconds)
Refer Table -1
(Default : 0)
User Offset
-19999 to 30000
(Default : 0)
0.0 to 60.0
(Default : 0.5 sec.)
Filter Constant
Refer Table -1
(Default : 1000)
PV Range Low
PV Range High
Disable
Enable
(Default : Disable)
Minimum Scale
Activation
Refer Table -1
(Default : 0)
Parameters
Settings
(Default Value)
INPUT CONFIGURATION PARAMETERS
Minimum Scale Value
Maximum Scale
Activation
Maximum Scale Value
Min. Scale to 30000
(Default : 0)
Square Root Value
Scan Rate
Slow
Medium
Fast
(Default : Fast)
Disable
Enable
(Default : Disable)
Disable
Enable
(Default : Disable)
0 to Max. Scale
(Default : 0)
0 to 20 mA
4 to 20 mA
0 to 50 mV
0 to 200 mV
0 to 1.25 V
0 to 5 V
0 to 10 V
1 to 5 V
0 to 20 mA DC current
4 to 20 mA DC current
0 to 50mV DC voltage
0 to 200mV DC voltage
0 to 1.25V DC voltage
0 to 5V DC voltage
0 to 10V DC voltage
1 to 5V DC voltage
-19999 to
30000 units
User settable
1 / 0.1 / 0.01 /
0.001 units
TABLE -1
FRONT PANEL LAYOUT
FRONT PANEL
ELECTRICAL CONNECTIONS
-19999 to 30000
(Default : 0)
None
Process Low
Process High
(Default : None)
(Default : Disable)
Disable
Enable
(Default : Normal)
Normal
Reverse
0 to 125
(Default : 0)
(Default : No)
No
Yes
(Default : No)
No
Yes
(Default : No)
No
Yes
(Default : No)
No
Yes
(Default : No)
No
Yes
(Default : No)
No
Yes
(Default : No)
No
Yes
0 to 250
(Default : 0)
0 to 30000
(Default :
For Process Low : 0,
For Process High : 1000)
0 to 30000
(Default :
For Process Low : 0,
For Process High : 1000)
0 to 99999999
(Default : 5000000)
0 to 125
(Default : 0)
KEYS OPERATION
Symbol
Key
Function
Press to Reset the Flow Total value to zero.
OPERATOR
SCROLL
Press to scroll through the various display
fields individually on Lower Readout in View
Only Mode.
Press to access the Operator Mode.
Press to manually Acknowledge the Rate /
Total Alarms if the Alarm latch is enabled.
RESET
DOWN
UP
ENTER
PAGE
ACKNOWLEDGE
Press to enter or exit set-up
mode
.
Press to store the set parameter value and
to scroll to the next parameter on the PAGE.
Press to increase the parameter value.
Pressing once increases the value by one
count; keeping pressed speeds up the
change.
Press to decrease the parameter value.
Pressing once decreases the value by one
count; keeping pressed speeds up the
change.
Upper Readout
Lower Readout
ENTER Key
UP Key
DOWN Key
PAGE Key
Alarm-2 TotaI Indicator
Alarm-1 TotaI Indicator
Alarm-1 Rate Indicator
Alarm-2 Rate Indicator
Reset Key
Acknowledge Key
Scroll Key
Operator Key
DC Linear
Analog
Input
Digital
Input-1
Digital
Input-2
NO
RLY
SSR / DC Lin
OP-5
C
NO
RLY
SSR
Total AL-2
C
NO
RLY
SSR
Total AL-1
C
NO
RLY
SSR
Flow AL-2
C
NO
RLY
SSR
Flow AL-1
C
B-
GND
SERIAL COMM
Ext. Voltage
L
N
85 ~ 265 V
AC SUPPLY
B+
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
31
32
33
34
35
36
37
38
39
21
22
23
24
25
26
27
28
29
30