Chapter 5 Function parameter
127
Code
Parameter name
Setting range
Factory
setting
Change
limits
F6.00
STOP/RESET key
functions
STOP/RESET key
is enabled only in
keyboard operation
mode
0
1
☆
STOP/RESET key
is enabled under
any
operation
mode
1
F6.01
Running status
display parameters 1
0000 to FFFF
001F
☆
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
DI Input status
Output torque
Output power
Output current
(Hz)
Bus voltage
(V)
Set frequency
Running frequency
Output voltage
DO Output
AI1 Voltage
AI2 Voltage
(Hz)
Count
Reserve
Length
Load speed
PID Setting
(A)
(kW)
(%)
(V)
(V)
(V)
If the above parameters need to be displayed in operation, firstly set its position to 1, and then
set at F6.01 after converting the binary number to the hexadecimal number.
F6.02
Running status
display parameters 2
0 to FFFF
0000
☆
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Present charge time
Line speed
Rest time of running
Running frequency2 (Hz)
High speed pulse input
frequency
(kHz)
PLC range
PID feedback
(Hour)
Present running time (Min)
High speed pulse input
frequency
(Hz)
Communication parameters
encoder feedback speed(Hz)
Assistance frequency B
display
(Hz)
Main frequency A
display
(Hz)
Ordering torque
Remain
Synchronous machine
wheel position
If the above parameters need to be displayed in operation, firstly set its position to 1, and
then set at F6.02 after converting the binary number to the hexadecimal number.
Running status display parameters, which is used to set the parameters that can be viewed
when the inverter is in operation.
There are 32 parameters available for viewing, select desired status parameters
according to F6.01, F6.02 binary parameter values, the display order starts from the lowest
level of F6.01.
F6.03
Stop status display parameters
0000 to FFFF
0033
☆