Chapter 8 Maintenance and repair
80
Ch
ap
ter 8
Voltage
AC 380V
Inverter
R
S
T
Figure 8-1:380V Drive equipment charging circuit example
8-5.Measuring and readings
※
If a general instrument is used to measure current, imbalance will exists for the current at the
input terminal. generally, the deviation is not more than 10%, that is normal. If the deviation
exceeds 30%, please inform the original manufacturer to replace rectifier bridge, or check if
the deviation of three-phase input voltage is above 5V or not.
※
If a general multi-meter is used to measure three-phase output voltage, the reading is not
accurate due to the interference of carrier frequency and it is only for reference.