background image

Z

ONE

M

ASTER

 PLUS

®

AC Panel Transient Voltage Surge Suppressors

Installation

Instructions

& User Manual

P

owerware TVSS

Содержание TVSS ZoneMaster PLUS

Страница 1: ...ZONEMASTER PLUS AC Panel Transient Voltage Surge Suppressors Installation Instructions User Manual Powerware TVSS...

Страница 2: ...ANEL PROTECTORS Particularly important is the length of the connecting leads see pages 4 5 INTRODUCTION This document explains how to install the Powerware TVSS ZoneMaster PLUS AC Panel Surge Protecti...

Страница 3: ...TVSS ZoneMaster PLUS units have comprehensive continuous visual status monitoring present on each module REMOTE INDICATORS A remote indication of the reduced protection state is available as a normal...

Страница 4: ...COMMENDED WIRE GAUGE Minimum of 8 AWG Maximum of 4 AWG for ease of dressing LENGTH OF CONNECTING LEADS The longer the connecting leads between the the ZoneMaster PLUS and power panel the higher the re...

Страница 5: ...5 RECOMMENDED CABLE DRESSING...

Страница 6: ...tic Connection Diagrams 6 120 240V SPLIT PHASE 3 W THREE PHASE 4W WYE THREE PHASE HIGH LEG DELTA NOTE L2 is designated as the HIGH LEG An optional breaker or disconnect may be used for overcurrent pro...

Страница 7: ...from the counter and reinstalled to the ZoneMaster PLUS wire lug Note If it is desired to measure surge currents on only a single individual phase insert selected phase connection wire through the tor...

Страница 8: ...lacement WARNING Before opening the access panel ensure that the AC supply has been disconnected Unplug the remote contact connector at the side of the module Remove the mounting screws on the module...

Отзывы: