8
Powerware 9315 Maintenance Bypass Module 30-160kVA
164201177 Rev. C 041500
1.
Carefully inspect the outer packaging for evidence of damage during transit.
CAUTION:
Do not install a damaged MBM. Report any damage to the carrier and contact
the local sales or service office immediately.
2.
Use a forklift or other material handling equipment to move the MBM to a
convenient unpacking area. Insert the forklift jacks between the laminated
plywood/polyfoam skids on the bottom of the unit.
CAUTION:
Do not tilt unit more than 10 degrees from vertical.
3.
Set the pallet on a firm, level surface, allowing a minimum clearance of
4.6m (15 ft) on each side for removing the MBM from the pallet.
4.
Cut the steel bands around the MBM.
5.
Remove the protective cardboard covering from the MBM, cutting where
indicated, using a knife blade no longer than 25 mm (1 in.).
NOTE:
Do not discard the packaging material. Instructions for unloading the MBM
from the pallet are printed on the cardboard. Please to refer to them.
6.
Remove the plastic bag and foam packing material. Please discard or recycle
them in a responsible manner.