background image

User Manual

PowerWalker VI TW Series

Uninterruptible Power Supply System 

Version: 1.0 

Содержание VI TW 1.1K

Страница 1: ...User Manual PowerWalker VI TW Series Uninterruptible Power Supply System Version 1 0...

Страница 2: ...tion And Setup 4 2 1 Rear panel view 4 2 2 Operating principle 5 2 3 Setup the UPS 5 3 Operations 7 3 1 Button operation 7 3 2 LCD Panel 7 3 3 Audible Alarm 8 3 4 LCD display wordings index 9 3 5 UPS...

Страница 3: ...Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system Please use only VDE tested CE marked or UL marked for 110 115 120 127 VAC models...

Страница 4: ...ries Released electrolyte is harmful to the skin and eyes It may be toxic a Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified be...

Страница 5: ...tial environment this product may cause radio interference in which case the user many be required to take additional measures only for 220 230 240 VAC system Only for 110 115 120 127 VAC system NOTE...

Страница 6: ...ace for future use 2 1 Rear panel view IEC Type 1 1K 1 5K 2K 3K NEMA Type 1 1K 1 5K 2K 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC...

Страница 7: ...nd door Maintain minimum clearance of 100mm in the bottom of the UPS to avoid dust and high temperature 2 Maintain an ambient temperature range of 0 C to 45 C for UPS optimal operation For every 5 C a...

Страница 8: ...sed a metal plate is connected to Pin 1 and Pin2 for UPS normal operation To activate EPO function remove two screws on EPO port and green connector will be removed Note The EPO function logic can be...

Страница 9: ...election key Press this button to confirm selection in UPS setting mode SELECT Button Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage b...

Страница 10: ...ion Indicates the load level by 0 24 25 49 50 74 and 75 100 Indicates overload Programmable outlets information Indicates that programmable management outlets are working Mode operation information In...

Страница 11: ...meters to set up the UPS Parameter 1 It s for program alternatives Refer to below table Parameter 2 is the setting options or values for each program 01 Output voltage setting Interface Setting Parame...

Страница 12: ...ng Interface Setting Parameter 2 Set up the charger maximum current 1 2 4 6 8 setting the maximum charger current at 1 2 4 6 8 Ampere Default 8A Note This setting is only effective for super charger 0...

Страница 13: ...Selection button for 3 seconds to enter Setting mode Step 3 Press the Up button ON MUTE to switch to 02 of program list Then press Enter button to enter value setting of parameter 2 Press the Up butto...

Страница 14: ...regulation range but higher than low loss point the boost AVR will be activated Battery mode When the input voltage is beyond the acceptable range or power failure UPS will backup power from battery...

Страница 15: ...every 2 seconds EPO enable Sounding every 2 seconds Over temperature Sounding every 2 seconds Charger failure Sounding every 2 seconds Battery fault Sounding every 2 seconds At this time UPS is off to...

Страница 16: ...nal or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 on LCD display and alarm is continuously sounding Battery voltage is too high or th...

Страница 17: ...ult your dealer Batteries defect Contact your dealer to replace the battery Fault code is shown as 45 on LCD display At the same time alarm is continuously sounding The charger does not have output an...

Страница 18: ...103 110 5 10 1 minutes 110 150 5 10 10 sec 150 5 10 0 5 sec EFFICIENCY AC Mode 96 Buck Boost Mode 95 Battery Mode 88 up to 90 nominal battery voltage BATTERY Battery Type Number 12 V 7 Ahx2 12 V 9 Ahx...