Service Manual
Chapter 5 - Functional description
Auxiliary Supply PCB CS0070
5 - 2
3x3 UPS Functional description
Issue 2 - November 2001
c)
J6ĆJ7ĆJ8 define the overload level related to the UPS ratings
Link
10K
20K
30K
J6
open
close
open
J7
close
open
close
J8
close
close
open
d)
J9ĆJ10ĆJ12 defines the inverter peak current limit for the appropriate UPS output rating.
Link
10K
20K
30K
J9
open
close
open
J10
open
open
close
J12
open
open
open
e)
J11 define the converter peak current limit. (normally closed for all UPS output ratings).
5.2 - Auxiliary Supply PCB CS0070
The auxiliary power supply is based on a flyĆback converter circuit, the source supply being the 750 volt
DC Bus. Secondary windings of the power supply transformer provide the control logic and the power
component gate drive circuits.
The auxiliary power supply generates a regulated 7. 5Vdc and l5Vdc voltage.
Adjustments to the battery threshold voltage are made from the auxiliary power supply by setting the
potientiometers P1, P2 and P3.
5.2.1 - Battery Threshold settings
a)
Maximum voltage (500 Vdc) adjusted with P1.
b)
Minimum voltage (320 Vdc) adjusted with P2.
c)
PreĆalarm voltage (350 Vdc) adjusted with P3.