4. Troubleshooting

If Commander RT series do not operate correctly, please solve the problem by using the table 
below.  

Symptom 

Possible cause 

Remedy 

No indication and alarm even 

though the mains is normal.  

The  AC  input  power  is  not 

connected well. 

Check  if  input  power  cord 

firmly  connected  to  the 
mains.  

The  AC  input  is  connected 
to the UPS output. 

Plug AC input power cord to 
AC input correctly.  

The icon 

and the warning 

code 

 flashing on LCD display 

and alarm is sounding  2 short 
beeps every 2 seconds 

EPO function is activated. 

Set  the  circuit  in  close 
position  to  disable  EPO 
function. 

The icon 

and 

 flashing on 

LCD display and alarm is sounding 
2 short beeps every 2 seconds 

Line and neutral conductors 
of UPS input are reversed. 

Rotate  mains  power  socket 
by  180°  and  then  connect 

to UPS system. 

The icon

 and 

flashing 

on LCD display and alarm is 
sounding 2 short beeps every 2 
seconds 

The external or internal 
battery is incorrectly 
connected. 

Check  if  all  batteries  are 
connected well. 

Fault code is shown as 27 and the 

icon 

 

is lighting on LCD display 

and alarm is continuously 
sounding. 

Battery  voltage  is  too  high 

or the charger is fault. 

Contact your dealer. 

Fault code is shown as 28 and the 

icon 

 

is lighting on LCD display 

and alarm is continuously 
sounding. 

Battery  voltage  is  too  low 
or the charger is fault. 

Contact your dealer. 

The icon 

 and the icon 

 

are flashing on LCD 

display and alarm is sounding 2 
short beeps every 2 seconds. 

UPS is overload 

Remove  excess  loads  from 
UPS output. 

Fault code is shown as 43 and The 
icon 

is lighting on LCD 

display and alarm is continuously 
sounding. 

The UPS shut down 
automatically because of 

overload at the UPS output. 

Remove  excess  loads  from 
UPS output and restart it. 

Fault code is shown as 14 and 
alarm is continuously sounding. 

The UPS shut down 
automatically because short 

circuit occurs on the UPS 
output. 

Check  output  wiring  and  if 
connected  devices  are  in 

short circuit status. 

Содержание 1100 VA

Страница 1: ...terruptible Power Supply System www powershield com au Commander RT 1100 2000 3000 VA Line Interactive Sinewave UPS IMPORTANT Download latest software www powershield com au downloads NetGuard User Ma...

Страница 2: ...ags power surges under voltage over voltage line noise frequency variation switching transients and harmonic distortions The Commander RTs will continuously protect your equipment by internally isolat...

Страница 3: ...nd the associated warning should be observed CAUTION REFER TO OPERATOR S MANUAL Refer to your operator s manual for additional information such as important operating and maintenance SAFETY EARTHING T...

Страница 4: ...he UPS 7 2 3 Setup the UPS 7 3 Operations 10 3 1 Button Operation 10 3 2 LCD Panel 10 3 3 Audible Alarm 11 3 4 LCD Display Wordings Index 12 3 5 UPS Setting 12 3 6 Operating Mode Description 15 3 7 Fa...

Страница 5: ...the UPS system near water or in moist environments Do not install the UPS system where it would be exposed to direct sunlight or near heater Do not block ventilation holes in the UPS housing 1 3 Inst...

Страница 6: ...nect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS capacitors Only persons are adequately familiar with...

Страница 7: ...r Panel View PSCRT1100 PSCRT2000 PSCRT3000 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC input 4 Input circuit breaker 5 Emergency po...

Страница 8: ...S input connection Plug the UPS into a two pole three wire grounded receptacle only Avoid using extension cords Step 2 UPS output connection There two kinds of outputs programmable outlets white colou...

Страница 9: ...UPS it will provide advanced communication and monitoring options NOTE USB port and RS 232 port cannot work at the same time Step 5 EPO Emergency Power OFF function Keep the pin 1 and pin 2 closed fo...

Страница 10: ...all software Install NetGuard UPS monitoring software to fully configure UPS shutdown Please follow steps below to download and install monitoring software 1 Go to the website http www powershield com...

Страница 11: ...d hold this button at least 2 seconds to turn off the UPS Confirm selection key Press this button to confirm selection in UPS setting mode SELECT Button Switch LCD message Press this button to change...

Страница 12: ...ion Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuited UPS status Indicates that programmable management outlets are wor...

Страница 13: ...or program alternatives There are 4 programs to set up output voltage setting programmable outlets enable disable programmable outlets setting LCD display direction and exit 01 Output voltage setting...

Страница 14: ...time limits in minutes from 0 999 for programmable outlets which connect to non critical devices on battery mode 04 LCD display direction setting Interface Setting RAC the LCD display is horizontal TO...

Страница 15: ...ss and hold the Selection button for 5 seconds to enter Setting mode Step 3 Press the Up button ON MUTE to switch to 02 of program list Then press Enter button to enter value setting of parameter 2 Pr...

Страница 16: ...s fully charged the fan will stop working for energy saving Buck mode when AC is normal When the input voltage is higher than the voltage regulation range but lower than high loss point the buck AVR w...

Страница 17: ...x Inverter voltage high 12 x Over load 43 Inverter voltage Low 13 x 3 8 Warning Indicator Warning Icon flashing Alarm Low Battery Rapid one beep every second Overload 2 short beeps every 2 seconds Ba...

Страница 18: ...ing 2 short beeps every 2 seconds The external or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 and the icon is lighting on LCD display...

Страница 19: ...uipped with internal batteries and user can replace the batteries without shutting down the UPS or connected loads hot swappable battery design Replacement battery pack is a safe procedure and isolate...

Страница 20: ...rst before installing it inside of UPS Please select correct battery kit procedure below to assemble it Battery kit for PSCRT1100 Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by f...

Страница 21: ...shells Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well Battery kit for PSCRT3000 PSRTBB12 Step 1 Remove adhesive tapes Step 2 Connect all battery terminal...

Страница 22: ...l to eliminate common problems 2 Verify that no input output circuit breaker are tripped A tripped circuit breaker is the most common problem 3 If the problem still persists please call 1300 305 393 f...

Страница 23: ...ring charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency C...

Страница 24: ...tems Linux Unix and Mac AC Mode Batt Mode Load Level Input Voltage Output Voltage Overload Fault Low Batt ProTeCTIon Full Protection Overload discharge thermal short circuit and overcharge protection...

Отзывы: