Advance: Maintainer Setting Menu Page 2
To access the “Advance
Maintainer” Setting menu page, it’s required to enter
password. Please contact your local dealer to get maintainer password.
CAUTION: This setting menu is only for qualified technician. Otherwise, mis-
operation will cause UPS damage.
There are
five
sub-menus under “Advance
Maintainer” setting: SYS
PARAMETER, INSTALL INFO, VOL CALI, CURR CALI, INITIAL,
ELECTRONIC, BATT, MISCELLANEOUS and UPS SELFTEST.
SYS PARAMETER
SYS PARAMETER Page 1
Model Name: Set the UPS model name.
Serial Number: Set the serial number.
Manufacturer: Set the UPS manufacturer.
Charger Number: The number of charging boards installed in the UPS.
NOTE: It’s required to restart the UPS after setting.
Max Charge Current:
One piece of charger: There are twelve options: 1A, 2A, 3A, 4A, 5A, 6A,
7A, 8A, 9A, 10A, 11A, 12A.
Two pieces of charger: There are twelve options: 2A, 4A, 6A, 8A, 10A, 12A,
14A, 16A, 18A, 20A, 22A, 24A